The Disposal Size Of The Cable End Should Follow The Dimensions Described In This Manual - Mitsubishi FX3UC SERIES User Manual

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.
• Make sure to properly wire the FX
precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.

- The disposal size of the cable end should follow the dimensions described in this manual.

- Tightening torque should be between 0.5 and 0.8 N
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.22 and 0.25 N
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N
WIRING PRECAUTIONS
• Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
• Before cleaning or retightening terminals cut off all phases of the power supply externally.
Failure to do so may cause electric shock.
• Make sure to connect the battery for memory backup correctly.
Do not charge, disassemble, heat, short-circuit, or expose the battery to fire.
Doing so may rupture or ignite it.
• Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual
and the associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
• The FX
-32MT-LT has a built-in power supply. When connecting the power supply adapter or dedicated power
3UC
supply for CC-Link/LT, connect the built-in master to the LINK connector in the power supply adapter or dedicated
power supply.
Connection to the LINK/POWER connector may cause failures.
Correct
connection
104
/FX
0N
2N
Power adapter or Dedicated
Power Supply
LINK
connector
LINK/
POWER
connector
/FX
Series extension equipment in accordance with the following
3U
m.
m.
m.
Wrong
Power adapter or Dedicated
connection
Power Supply
3 Generic Specifications/Installation Work
LINK
connector
LINK/
POWER
connector

Advertisement

Table of Contents
loading

Table of Contents