5.4.16 BFM #71 to #74: Lower limit error setting / BFM #81 to #84: Upper limit error setting

Set the upper/lower limit error data so that the upper/lower limit error status (BFM #26) can be detected.
The data setting range depends on the input mode set in BFM #0.
The following table shows the data setting range for each input mode:
Input mode (BFM #0)
Set
value
Voltage input
0
(-10V to +10V: -32000 to +32000)
Voltage input
1
(-10V to +10V: -4000 to +4000)
Voltage input
2
Analog value direct indication mode
(-10V to +10V:-10000 to +10000)
Current input
3
(4mA to 20mA:0 to 16000)
4
Current input (4mA to 20mA:0 to 4000)
Current input
5
Analog value direct indication mode
(4mA to 20mA:4000 to 20000)
Current input
6
(-20mA to +20mA:-16000 to +16000)
Current input
7
(-20mA to +20mA:-4000 to +4000)
Current input
8
Analog value direct indication mode
(-20mA to +20mA:-20000 to +20000)
1. Cautions regarding upper/lower limit error setting
• To use the set upper/lower limit error data, be sure to turn on the upper/lower limit error detection function
(b1 of BFM #22).
• To use the data addition function (b0 of BFM #22) together with this function, be sure to add the addition
data (channels 1 to 4: BFM #61 to #64) to the upper/lower limit values to be set. In addition, observe the
data setting range.
Description
Numeric data type: Decimal (K)
Lower limit value
Setting range
(Channels 1 to 4:
BFM #71 to #74)
-32768 to +32767
-32768
-4095 to +4095
-4095
-10200 to +10200
-10200
-1 to +16383
-1
-1 to +4095
-1
3999 to 20400
3999
-16384 to +16383
-16384
-4096 to +4095
-4096
-20400 to +20400
-20400
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
Setting range: See below.
Initial value: See below.
Initial value
Upper limit value
(Channels 1 to 4:
BFM #81 to #84)
32767
4095
10200
16383
4095
20400
16383
4095
20400
B-41
A
B
C
D
E
F
G
H
I
J