9.18.13 Detailed remote station information [BFM #32 (20h) to #95 (5Fh)]

The information (I/O type, number of points) on remote stations is stored here.
In CONFIG mode, the contents of these BFMs can be changed.
→ For details on the changing method, refer to Section "9.13 Editing the detailed remote station
1.
Buffer memory assignment
Buffer memory No.
BFM #32 (20h)
BFM #33 (21h)
BFM #95 (5Fh)
2.
Description of detailed remote station information [BFM #32 (20h) to #95 (5Fh)]
Bit
b0
b1
b2
Number of I/O points
b3
b4
b5 to b7 (Setting prohibited)
b8
Input flag
b9
Output flag
b10
RD station flag
b11
Head station flag
b12
Input filter setting
b13
Output hold/clear setting
b14
(Setting prohibited)
b15
Reserved station flag
3. Number of I/O points (b4 to b0)
The number of I/O points used in the BFM dependent station number is stored here.
The maximum number of points is 4 or 16 in accordance with the number of points per station set by the DIP
switch for operation setting.
When a remote I/O unit with 16 I/O points is used in 4-point mode, the number of points per buffer memory is
4, and the I/O points of the remote I/O unit are assigned to four buffer memories.
In the case of a composite I/O unit, the larger quantity between the number of input points and the number of
output points is stored here.
In the case of a remote device station, 16 points are stored here.
4. Input flag (b8) and output flag (b9)
The type of the corresponding remote module (input unit, output unit, composite I/O unit or remote device
station) is stored here.
b9: Output flag
0
1
1
5. RD station flag (b10)
When the station is a RD station, "1 (ON)" is stored.
When one unit occupies two or more stations, this bit is set to ON in the corresponding stations.
316
Remote station information area for the station No.1
Remote station information area for the station No.2
Remote station information area for the station No.64
Function
Points 1
b0
b1
b2
b3
b4
This is not the head station.
This is specified as a reserved station.
b8: Input flag
1
0
1
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
Description
0(OFF)
2
3
4
5
6
7
1
0
1
0
1
0
1
0
1
1
0
0
1
1
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Set these bits to 0.
Input is not given.
Output is not given.
It is not a RD station.
General-purpose input
CLEAR
Set these bits to 0.
Input unit
Output unit
Composite I/O unit or remote device station
9.18 Details of buffer memory
1(ON)
8
9 10 11 12 13 14 15 16
0
1
0
1
0
1
0
0
0
1
1
0
0
1
0
0
0
0
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
Input is given.
Output is given.
It is a RD station.
This is the head station.
High-speed input
HOLD
This is not specified as a reserved
station.
Unit type
information".
1
0
1
0
1
0
1
0
0
1