Hazardous Location Installation - For USA and Canada

General
This product has been designed with the intention of meeting the requirements of Class I, Division
2 hazardous location application. Division 2 locations are those locations where ignitable
concentrations of flammable substances are normally confined, prevented by ventilation, or
present in an adjacent Class I, Division 1 location, but where an abnormal situation might result in
intermittent exposure to such ignitable concentrations.
While this product is a non-incendive device under ANSI/ISA 12.12.01 and CSA C22.2 N213, it is
not designed for, and should never be used within a Division 1 (normally hazardous) location.
This product is suitable for use in Class I, Division 2, Groups A, B, C, and D hazardous locations
or in non-hazardous locations. Before installing or using this product, confirm that the ANSI/ISA
12.12.01 or CSA22.2 N213 certification appears on the product labeling.
NOTE: Some products are not yet rated as suitable for use in hazardous locations. Always use
your product in conformance with the product labeling and this manual.
POTENTIAL FOR EXPLOSION
Do not use this product in hazardous environments or locations other than Class I, Division 2,
Groups A, B, C, and D.
Substitution of any component may impair suitability for Class I, Division 2.
Do not connect or disconnect this product unless power has been switched off or the area is
known to be non-hazardous.
Always confirm that this product is suitable for use in hazardous locations by checking the
ANSI/ISA 12.12.01 or CSA C22.2 N213 certification appears on the product labeling.
Do not install any Pro-face or OEM components, equipment, or accessories unless these have
also been qualified as suitable for use in Class I, Division 2, Groups A, B, C, and D locations.
Do not attempt to install, operate, modify, maintain, service, or otherwise alter this product
except as permitted in this manual. Unpermitted actions may impair the suitability of this
product for Class I, Division 2 operation.
Failure to follow these instructions will result in death or serious injury.
POTENTIAL FOR EXPLOSION
Always confirm the ANSI/ISA 12.12.01 or CSA C22.2 N213 hazardous location rating of your
device before installing or using it in a hazardous location.
To apply or remove the supply power from this product installed in a Class I, Division 2
hazardous location, you must either:
Use a switch located outside the hazardous environment, or;
Use a switch certified for Class I, Division 1 operation inside the hazardous area.
Do not connect or disconnect equipment unless power has been switched off or the area is
known to be non-hazardous. This applies to all connections including power, ground, serial,
parallel, and network connections.
Never use unshielded / ungrounded cables in hazardous locations.
Use only non-incendiary USB devices.
When enclosed, keep enclosure doors and openings closed at all times to avoid the
accumulation of foreign matter inside the workstation.
Failure to follow these instructions will result in death or serious injury.
DANGER
DANGER