DC Power Cord Preparation
Make sure the ground wire is either the same or heavier gauge than the power wires.
Do not use aluminum wires in the power supply's power cord.
To prevent the possibility of a terminal short, use a pin terminal that has an insulating sleeve.
If the ends of the individual wires are not twisted correctly, the wires may create a short circuit.
The conductor type is solid or stranded wire.
Use copper wire rated for 75 C (167F).
Power Cord Diameter
Conductor type
Conductor length
Recommended Driver
Recommended Pin Terminals
Recommended Pin Terminal Crimp
*2
Tool
*1 For UL compatibility, use AWG14 or AWG13.
*2 Items are manufactured by Phoenix Contact.
0.75...2.5 mm
Solid or stranded wire
SZS 0.6x3.5 (1205053)
*2
3201288 AI 0,75-10 GY
*2
3200182 AI 1 -10 RD
3200195 AI 1,5 -10 BK
3202533 AI 2,5 -10 BU
CRIMPFOX 6
2
*1
(18...13 AWG)