007-4772-002
Table 4-2
L1 Controller Messages (continued)
L1 System Controller Message
Temperature messages: low alt.
ATTN: TEMP # advisory temperature reached
@ xxC xxF
ATTN: TEMP # critical temperature reached
@ xxC xxF
ATTN: TEMP # fault temperature reached
@ xxC xxF
Temperature messages: high alt.
ATTN: TEMP # advisory temperature reached
@ xxC xxF
ATTN: TEMP # critical temperature reached
@ xxC xxF
ATTN: TEMP # fault temperature reached @
xxC xxF
Temperature stable message:
ATTN: TEMP # stabilized @ xxC/xxF
Power off messages:
Auto power down in xx seconds
Base module appears to have been powered
down
Serial number messages:
Invalid System Serial Number format
No assigned System Serial Number
General Troubleshooting
Message Meaning and Action Needed
The ambient temperature at the module's air
inlet has exceeded 30º C.
The ambient temperature at the module's air
inlet has exceeded 35º C.
The ambient temperature at the module's air
inlet has exceeded 40º C.
The ambient temperature at the module's air
inlet has exceeded 27º C.
The ambient temperature at the module's air
inlet has exceeded 31º C.
The ambient temperature at the module's air
inlet has exceeded 35º C.
The ambient temperature at the module's air
inlet has returned to an acceptable level.
The L1 controller has registered a fault and is
shutting down. The message displays every
five seconds until shutdown.
The L1 controller has registered a fault and has
shut down.
See L1 log for details.
See L1 log for details.
109