IBM RS/6000 Enterprise Server M80 Service Manual page 207

Hide thumbs Also See for RS/6000 Enterprise Server M80:
Table of Contents

Advertisement

Table 5. SPCN Error Codes (continued)
Error Code Description
1041 1B05 Load fault on 1.8
1041 1B06 Load fault on 2.5
1041 1B07 Load fault on 2.5
1041 2600 Pgood fault
1041 2601 Pgood fault
1041 2603 Secondary I/O drawer power domain fault
1041 2612 SPCN problem
1041 3100 I2C controller fault
1041 3101 I2C bus 1 fault
1041 3102 I2C bus 2 fault
1041 3104 I2C bus 4 fault
Action/
Possible Failing FRU
1. I/O drawer power supply
Location: U0.4-V1
2. If power supply U0.4-V2 is present (no
cooling unit), use the power supply you
removed from U0.4-V1 to replace
U0.4-V2
3. Secondary I/O backplane
Location: U0.4-P1
1. I/O drawer power supply
Location: U0.4-V1
2. If power supply U0.4-V2 is present (no
cooling unit), use the power supply you
removed from U0.4-V1 to replace
U0.4-V2
3. Secondary I/O backplane
Location: U0.4-P1
1. I/O drawer power supply
Location: U0.4-V1
2. If power supply U0.4-V2 is present (no
cooling unit), use the power supply you
removed from U0.4-V1 to replace
U0.4-V2
3. Secondary I/O backplane
Location: U0.4-P1
Secondary I/O backplane
Location: U0.4-P1
Secondary I/O backplane
Location: U0.4-P1
1. Check input power to power supplies
Locations: U0.4-V1
U0.4-V2
2. I/O drawer power supplies
Locations: U0.4-V1
U0.4-V2
3. I/O Drawer Power Distribution Board
Location: U0.4-X1
4. Secondary I/O backplane
Location: U0.4-P1
Secondary I/O backplane
Location: U0.4-P1
Secondary I/O backplane
Location: U0.4-P1
1. Secondary I/O drawer operator panel
Location: U0.4-L1
2. Secondary I/O backplane
Location: U0.4-P1
Secondary I/O backplane
Location: U0.4-P1
Secondary I/O backplane
Location: U0.4-P1
Chapter 5. Error Code to FRU Index
189