Table 5. SPCN Error Codes (continued)
Error Code Description
1031 7650 Slow I/O drawer fan 5 in power supply 1
1031 7651 Missing I/O drawer fan 5 in power supply 1
1031 7660 Slow I/O drawer fan 6 in I/O drawer power
supply 2
1031 7661 Missing I/O drawer fan 6 in I/O drawer power
supply 2
1031 7690 Slow I/O drawer fan 9 in cooling unit
1031 7691 Missing I/O drawer fan 9 in cooling unit
1031 8400 VPD configuration problem
1031 8401 VPD access problem
1031 840A VPD +5 stuck high
1031 840B VPD +5 stuck low
1031 840D I/O type mismatch
1031 840E SPCN default configuration loaded
Action/
Possible Failing FRU
1. I/O drawer power supply 1
Locaton: U0.3-V1
2. Fan controller card
Locaton: U0.3-X2
3. I/O drawer power distribution board
Location: U0.3-X1
I/O drawer power supply 1
Location: U0.3-V1
1. I/O drawer power supply 2
Locaton: U0.3-V2
2. Fan controller card
Locaton: U0.3-X2
3. I/O drawer power distribution board
Location: U0.3-X1
I/O drawer power supply 2
Location: U0.3-V2
1. Fan 9 (cooling unit)
Locaton: U0.3-F9
2. Fan controller card
Locaton: U0.3-X2
3. I/O drawer power distribution board
Location: U0.3-X1
Fan 9 (cooling unit)
Location: U0.3-F9
1. Check for system firmware update
2. Call second level of support
1. Check for system firmware update
2. Call second level of support
Secondary I/O backplane
Location: U0.3-P1
Secondary I/O backplane
Location: U0.3-P1
1. Check cabling
2. From the main service processor menu,
select the System Information Menu,
then select the Power Control Network
Utilities Menu. Use option three to set
the I/O type to 84. Reboot the system.
3. Primary I/O drawer backplane
Location: U0.1-P1
1. Check cabling
2. From the main service processor menu,
select the System Information Menu,
then select the Power Control Network
Utilities Menu. Use option three to set
the I/O type to 84. Reboot the system.
3. Primary I/O drawer backplane
Location: U0.1-P1
Chapter 5. Error Code to FRU Index
185