Check Points; Periodical Inspection - Toshiba TOSVERT VF-MB1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

Check points

1. Something unusual in the installation environment
2. Something unusual in the cooling system
3. Unusual vibration or noise
4. Overheating or discoloration
5. Unusual odor
6. Unusual motor vibration, noise or overheating
7. Adhesion or accumulation of foreign substances (conductive substances)
Cautions about cleaning
To clean the inverter, wipe dirt off only its surface with a soft cloth but do not try to remove dirt or stains from any
other part. If stubborn stains persist, remove them by wiping gently with a cloth dampened with neutral detergent
or ethanol.
Never use any of the chemicals in the table below; the use of any of them may damage or peel the coating away
from molded parts (such as plastic covers and units) of the inverter.
Acetone
Benzen
Chloroform

14.2 Periodical inspection

Make a periodical inspection at intervals of 3 or 6 months depending on the operating conditions.
Mandatory
action
Prohibited
14
 Before inspection, perform the following steps.
(1) Shut off all input power to the inverter.
(2) Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit.
(3) Use a tester that can measure DC voltages (400V/800V DC or more), and check that the voltage to
the DC main circuits (across PA-PC) does not exceed 45V.
Performing an inspection without carrying out these steps first could lead to electric shock.
 Never replace any part.
This could be a cause of electric shock, fire and bodily injury. To replace parts, call your Toshiba
distributor.
Ethylene chloride
Ethyl acetate
Glycerin
Warning
N-2
E6581697
Tetrachloroethane
Trichloroethylene
Xylene