6.29.3 Displaying the motor or the line speed
f702 : Frequency free unit display magnification
f703 : Frequency free unit coverage selection
f705 : Inclination characteristic of free unit display
f706 : Free unit display bias
 Function
The value obtained by multiplying the displayed frequency by the f702 -set value will be displayed as
follows:
Value displayed = Monitor-displayed or parameter-set frequency  f702
6
1)
2)
The frequency or any other item displayed on the monitor can be converted freely into the rotational
speed of the motor, the operating speed of the load, and so on.
Using these parameters, the units of the amounts of processing and feedback in PID control can also
be changed.
Displaying the motor speed
To switch the display mode from 60Hz (default setting) to 1800min

=.
Displaying the speed of the loading unit
To switch the display mode from 60Hz (default setting) to 6m/min
 
Hz
=.
Note: This parameter displays the inverter output frequency as the value obtained by multiplying it by a
positive number. This does not mean that the actual motor speed or line speed are indicated
with accuracy.

Hz
=
×.=
=.
×.=.
F-106
-1
(the rotating speed of the 4P motor)
-1
(the speed of the conveyer)

E6581697