Toshiba TOSVERT VF-MB1 Instruction Manual page 225

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

6.29.2 Changing the unit (A/V) from a percentage of current
and voltage
f701 :Current/voltage unit selection
 Function
These parameters are used to change the unit of monitor display.
%  A (ampere)/V (volt)
Current 100% = Rated current of inverter
Input/output voltage 100% = 200Vac (240V class), 400Vac (500V class)
Example of setting
During the operation of the VFMB1S-2015PL (rated current: 8.0A) at the rated load (100% load), units are
displayed as follows:
1) Display in percentage terms
%
Output current:
 
%
Input voltage:
 
[Parameter setting]
Title
Function
Current/voltage unit
f701
selection
*
The f701 converts the following parameter settings:
 A display : Current monitor display: Load current, torque current
Motor electronic-thermal protection level 1 & 2
DC braking current
Stall prevention level 1 & 2
Small current detection current
 V display : Input voltage, output voltage
Note) Base frequency voltage 1 & 2(  ,  ) always displayed in the unit of V.
2) Display in amperes/volts

100%

100%
0: %
1: A (ampere) / V (volt)
F-105
Output current:
8.0A
Input voltage:
200V
Adjustment range
 , f173
f251
f601 , f185
f611
E6581697
6
Default setting
0

Hide quick links: