6.24.10 Over-torque trip
f615 : Over-torque trip/alarm selection
f616 : Over-torque detection level
f618 : Over-torque detection time
f619 : Over-torque detection hysteresis
 Function
If the torque value exceeds the value set at f616 and doesn't return below f616 - f619
for a time that exceeds the value set at f618 , tripping or output alarm will be activated.
ot is displayed in the event of a trip.
f615 = 0 : No tripping. (Failure signal FL not activated)
An over-torque alarm can be put out by setting the output terminal function selection parameter.
f615 = 1 : The inverter is tripped (Failure signal FL activated) only after a torque exceeding the f616 -
specified level has been detected for more than the f618 -specified time.
[Parameter setting]
Title
Over-torque trip/alarm selection
f615
f616
Over-torque detection level
Over-torque detection time
f618
Over-torque detection hysteresis
f619
Note: f618 = 0.0 seconds is the shortest time detected on control.
Function
0: Alarm only
1: Tripping
0 (disabled),
1-250 (%)
0.0-10.0 (s)
0-100 (%)
F-87
Adjustment range
Default setting
Note
E6581697
6
0
150
0.5
10