6.4

Basic parameters 2

6.4.1
f170 : Base frequency 2
f171 : Base frequency voltage 2
f172 : Torque boost value 2
f173 : Motor electronic-thermal protection level 2
f185 : Stall prevention level 2
 Function
6
[Parameter setting]
f170
f171
f172
f173
f185
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: The inverter's rated current is 100%. When f701 (current and voltage unit selection)
= 1 (A (amps)/V (volts)) is set, it can be set at A (amps).
Switching motor characteristics via terminal input
Use the above parameters to switch the operation of two motors with a single inverter and to select
motor V/F characteristics (two types) according to the particular needs or operation mode.
Note: The pt (V/F control mode selection) parameter is enabled only for motor1.
If motor 2 is selected, V/F control will be given constant torque characteristics.
Title
Function
Base frequency 2
Base frequency voltage 2
Torque boost value 2
Motor electronic-thermal
protection level 2
Stall prevention level 2
Adjustment range
20.0-500.0
50-330 (V) (240V class)
50-660 (V) (500V class)
0.0-30.0 (%)
10-100 (%) / (A)
*2
10-199 (%) / (A),
200 : Disabled
*2
F-10
E6581697
Default setting
*1
*1
Depending on model
(Refer to section 11.4)
100
150