PRECAUTIONS

Grounding Requirements

The system grounding must have a specific ground resistance and AC noise level, and is to be connected
to a predetermined terminal in the PBX. Standard grounding requirements are as shown below:
• Communication grounding: Less than 10 Ω
• Protective ground for PIM : Less than 10 Ω
NOTE:
The AC ripple on these various grounds should be less than 1/2 Vp-p.
Grounding circuit continuity is vital for safe operation of telecommunication equipment.
Never operate this equipment with the grounding conductor disconnected.
The following specific requirements apply to ground wiring.
Install an equipment grounding conductor that is at least the same size as the ungrounded branch-
supply conductors as part of the circuit that supplies the PBX. The main grounding conductor shall
be green with one or more yellow stripes. Or the equipment grounding conductors shall have a
continuous outer finish that is green. The equipment grounding connector is to be connected to
ground at the service equipment. For details of wiring connections, see
TO
TERMINALS".
The attachment-plug receptacles near the PBX are all to be of a grounding type, and the equipment
grounding conductors serving these receptacles are to be connected to earth ground at the service
equipment.
CAUTION
Page 76
– 62 –
CHAPTER 2 INSTALLATION

PRECAUTIONS

"WIRING POWER CABLE
NWA-008841-001 Rev.5.0
90ch2001.fm
OCTOBER/19/2006