T R U M A CO MB I FAU LT F I N DI NG & A LDE H E AT ING
Fault
When the device is switched
on in electrical operation the
red LED on the control panel
flashes, the yellow LED on
the power selector switch
does not illuminate and the
heater does not heat up
If these measures do not remove the
failure, please contact the Truma Service
Centre.

ALDE COMPACT 3010

Challenger and Eccles SE, Conqueror,
Elite and Cameo based models
Please read these instructions carefully
before using the boiler.
These instructions are approved for The Alde
Compact 3010 boiler fitted in caravans, motor
caravans and buildings in accordance with CE
no. EMC e5 02 0138, 845 BP-0003.
Installation and repairs may only be carried out
by a professional. National regulations must be
adhered to.
BOILER DESIGN
The boiler consists of three eccentrically- fitted
cylinders (heat exchanger, water jacket for the
heating system and, outermost, water jacket
for hot water). The two outer pipes, and their
ends and connections, are made of stainless
106
Cause
- No 230 V operating voltage
- 230 V fuse defective
- Overheating protection has
activated
steel, while the heat exchanger is made of
aluminium.
The heat exchanger is divided into two semi-
circles. The burner is located in the upper
half, being the combustion chamber, and
the combustion gases are expelled through
the lower half. The burner unit is fitted on the
end of the heat exchanger. It consists of a
combustion fan, burner, solenoid valve and
intake/exhaust connections. Two heating
cartridges are fitted to the water jacket of the
heating system. Maximum output is 2 or 3 kW,
depending on model.
DESCRIPTION OF FUNCTIONS
Using LPG
When LPG operation is selected on the control
panel, the combustion fan starts. When the
fan speed is correct, it signals the circuit
board that the boiler can be lit. The circuit
board sends ignition sparks to the spark plug
at the same time as it sends electricity to the
solenoid valve, which opens to allow gas in.
The burner ignites, and a sensor transmits a
signal back to the circuit board that the boiler
is lit, and the ignition spark stops. The burner
keeps burning until the boiler thermostat or the
room thermostat reaches the set temperature
reading.
Should the boiler go out for any reason, the
sensor is activated and a new attempt is made
to start the boiler (in about 10 seconds).
Rectification
- Check 230 V operating
voltage
- Check 230 V fuse and
replace if necessary
- Reset overheating
protection. Allow heater to
cool, remove connection
cover and press reset
button