Retry function (Pr. 65, Pr. 67 to Pr. 69)

Pr. 65 "retry selection"
Pr. 67 "number of retries at alarm occurrence"
Pr. 68 "retry waiting time"
Pr. 69 "retry count display erasure"
When an alarm occurs, the retry function causes the inverter to automatically reset itself to make a restart
and continue operation. You can select whether retry is made or not, alarms reset for retry, number of retries
made, and waiting time.
Parameter
Factory Setting
Number
65
0
67
0
68
1 s
69
0
<Setting>
Use Pr. 65 to select alarms to be reset for retry.
Errors Reset for Retry
Display
0
z
E.OC1
E.OC2
z
E.OC3
z
E.OV1
z
z
E.OV2
E.OV3
z
E.THM
z
E.THT
z
E.IPF
z
z
E.UVT
E.FIN
E. BE
z
E. GF
z
E. LF
z
E.OHT
E.OLT
z
E.OPT
z
E.OP1
z
E.OP2
z
z
E.OP3
E. PE
z
E.PUE
E.RET
E.CPU
E.E6
E.E7
E.MB1
z
E.MB2
z
E.MB3
z
z
E.MB4
E.MB5
z
E.MB6
z
E.MB7
z
E.P24
E.CTE
Note:
indicates the errors selected for retry.
z
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting Range
0 to 5
0 to 10, 101 to 110
0 to 10 s
0
Setting
1
2
3
4
5
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
91
PARAMETERS

Advertisement

Table of Contents
loading

Table of Contents