9 Operation
9.2.3 Setup Procedure Using Linear Servomotors without Hall Sensors
(d) Troubleshooting for Polarity Detection Errors
Refer to the following table for troubleshooting if polarity detection is not completed normally.
No.
Problem
The linear
servomotor
does not move
during polarity
detection
(speed
feedback is 0).
1
Polarity
detection error
alarm (A.C5)
has occurred.
2
9-20
Cause
Polarity
Check whether the status display is P-dt when the /S-ON (/P-DET) signal is input.
detection is not
If P-dt is not displayed, check whether the parameters for input signal selection Pn50A
and Pn50D are set correctly, and check whether signal input is being performed cor-
being
rectly.
performed.
A force limit is
To prevent danger during setup, the SGDH SERVOPACK's factory settings for the
force limit parameters are 30%.
activated.
Check the set values for Pn483 and Pn484, and change to a user-set value if the setting
is initial value. Increase the value to the maximum value if no particular restrictions are
required.
The mechanical
When the mechanical friction is relatively larger than the linear servomotor's rated
friction is large.
force (10% or more), the linear servomotor may stop operating during polarity detec-
tion if factory settings are used.
First, check whether the mass ratio (Pn103) is set correctly.
If Pn103 is set correctly, increase the value set for polarity detection speed loop gain
(Pn481).
If the load is heavy and the mechanical friction is very large, a large gain will cause an
alarm. The gain cannot be increased under this condition, so reduce the mechanical
friction.
If the mechanical friction cannot be reduced without difficulty and the situation does
not improve even if the gain is reduced, consider using the hall sensor for polarity
detection.
Overtravel
If the OT signal is detected during polarity detection, polarity detection will be ended
signal is
and the status will be returned to previous status.
Before performing polarity detection, move the linear servomotor to a position where
detected during
the OT signal is not detected.
polarity
detection.
Parameter
The settings for scale pitch (Pn280) and motor phase selection (Pn080.1) may not be
appropriate for the device. Check the linear scale specifications and feedback signal
settings are
conditions.
incorrect.
Noise is present
When the detection reference is repeatedly output several times in the same direction,
in the scale
noise may occur in the scale signal, resulting in malfunction. Check that the FG of the
serial converter unit and linear servomotor is connected to FG of the SERVOPACK,
signal.
and that FG of the SERVOPACK is connected to the power supply FG.
Also check that the encoder cable is securely sealed.
The coil
If the coil assembly is subjected to an external force such as cable tension, and the
assembly is
speed feedback is not 0 regardless of a 0 detection reference, polarity detection will be
poor. Reduce the external force and make the speed feedback 0.
being subjected
to an external
force.
When the linear scale pitch is 100 µm min, the SERVOPACK cannot detect correct
The linear scale
speed feedback.
precision is
Use a linear scale with good scale pitch precision (within 40 µm is recommended).
rough.
Linear
When the size of the speed feedback for the polarity detection reference is 2 mm/s max,
servomotor
detection may be poor.
First, check that the mass ratio (Pn103) is set correctly.
traceability for
If Pn103 is set correctly, increase the value of polarity detection speed loop gain
the polarity
(Pn481).
detection
When the load is heavy, a large gain will cause an alarm. The gain cannot be increased
reference is
under this condition, so reduce the mechanical friction.
poor.
If the mechanical friction cannot be reduced without difficulty, consider using the hall
sensor for polarity detection.
The travel
An alarm will occur if the linear servomotor movement distance exceeds 10 mm during
polarity detection. The linear servomotor may have moved during detection for some
distance during
reason, so check other causes and take appropriate countermeasures.
polarity
detection has
exceeded 10
mm.
Countermeasure