Fan mode behavior

In nonredundant fan mode, a fan failure or a missing fan causes:
The system Health LED to flash amber.
The operating system to orderly shutdown.
In redundant fan mode:
A fan rotor failure will switch the system to nonredundant fan mode.
This change is indicated by the Health LED flashing amber. The system continues to operate normally in this
mode.
A second fan rotor failure or a missing fan causes the operating system to orderly shutdown.

Installing a fan

Procedure
1.
If installed, remove the front bezel.
2.
Power down the server.
3.
Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
4.
Disconnect all peripheral cables from the server.
5.
Do one of the following:
Extend the server from the rack.
Remove the server from the rack.
6.
Remove the access panel.
7.
Remove the air baffle.
8.
Determine which fan blanks need to be removed to install the additional fans.
9.
Remove the fan blank.
Fan redundancy Bay 1
Yes
Fan
No
Blank
Yes
Fan
Bay 2
Bay 3
Bay 4
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Bay 5
Bay 6
Fan
Fan
Fan
Fan
Fan
Fan