System battery replacement
System battery information
The server contains an internal lithium manganese dioxide, a vanadium pentoxide, or an alkaline battery that provides
power to the real-time clock. If this battery is not properly handled, a risk of the fire and burns exists. To reduce the risk of
personal injury:
•
Do not attempt to recharge the battery.
•
Do not expose the battery to temperatures higher than 60°C (140°F).
•
Do not expose the battery to extremely low air pressure as it might lead to explosion or leakage of flammable liquid or
gas.
•
Do not disassemble, crush, puncture, short external contacts, or dispose the battery in fire or water.
•
If the server no longer automatically displays the correct date and time, then replace the battery that provides power
to the real-time clock. Under normal use, battery life is 5 to 10 years.
Removing and replacing the system battery
Procedure
1.
Power down the server.
2.
Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3.
Disconnect all peripheral cables from the server.
4.
Do one of the following:
•
Extend the server from the rack.
Remove the server from the rack.
•
5.
Remove the access panel.
6.
If installed, remove the secondary riser cage.
7.
Locate the system battery on the system board.
8.
Remove the system battery.