Fan mode behavior

In nonredundant fan mode, a fan failure or a missing fan causes:
The system Health LED to flash amber.
The operating system to orderly shutdown.
In redundant fan mode:
A fan rotor failure will switch the system to nonredundant fan mode.
This change is indicated by the Health LED flashing amber. The system continues to operate normally in this
mode.
A second fan rotor failure or a missing fan causes the operating system to orderly shutdown.

Installing a fan

CAUTION: To prevent improper cooling and thermal damage, do not operate the server unless all bays are
populated with either a component or a blank.
Procedure
1.
Back up all server data.
2.
If installed, remove the front bezel.
3.
Power down the server.
4.
Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
5.
Disconnect all peripheral cables from the server.
6.
Do one of the following:
Extend the server from the rack.
Remove the server from the rack.
7.
Remove the access panel.
8.
To determine which fan blanks to remove to install the additional fans, see Fan population guildlines on page 57.
9.
Remove the fan blank.
58
Hardware options installation