System battery replacement
System battery information
The server contains an internal lithium manganese dioxide, a vanadium pentoxide, or an alkaline battery that provides
power to the real-time clock. If this battery is not properly handled, a risk of the fire and burns exists. To reduce the risk of
personal injury:
•
Do not attempt to recharge the battery.
•
Do not expose the battery to temperatures higher than 60°C (140°F).
•
Do not expose the battery to extremely low air pressure as it might lead to explosion or leakage of flammable liquid or
gas.
•
Do not disassemble, crush, puncture, short external contacts, or dispose the battery in fire or water.
•
If the server no longer automatically displays the correct date and time, then replace the battery that provides power
to the real-time clock. Under normal use, battery life is 5 to 10 years.
Replace the system battery
Prerequisites
Before you perform this procedure make sure you have a small flat-bladed, nonconductive tool available.
Procedure
1. Power down the server.
2. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3. Do one of the following:
Extend the server from the rack.
•
Remove the server from the rack.
•
4. Remove the access panel.
5. If installed, remove the tertiary riser cage.
6. Locate the battery on the system board.
7. Use a small flat-bladed, nonconductive tool to carefully lift the front of the battery from the socket.
8. Remove the battery.
System battery replacement