7 -PARAMETERS OVERVIEW
Par.
Modbus Mnemonic Description
755 02F3H
ms_c_kp
M/S Cool Proport. Gain
756 02F4H
ms_c _ti
M/S Cool Integral Time
757 02F5H
ms_c _ts
M/S Cool Sampling Time
758 02F6H
ms_pmp
Master/Slave Pump Type
761 02F8H
JBUS_J6 JBus on J6 port
762 02FAH
jbus_add
JBus Slave Address
763 02FBH
jbus_bdr
JBus Baud Rate
764 02FCH
jbus_frm
JBus Frame Type
765 02FDH
jbus_tmt
JBus Comm. Timeout
031DH
797
unlock
Software Protection Code
031EH
799 031FH
password Current Password

7.2 - Description of customized DI/DO configurations

Par.
Description
501
Customized DI#7 Config
502
Customized DI#8 Config
503
Customized DI#9 Config
504
Customized DO#5 Config
505
Customized DO#8 Config
506
Customized DO#9 Config
80
Min
Max
-10
0,001
10
240
10
240
2 = Individual Water Pump: running 
according to M/S Overrall Status
2
3
(Par.229), 3 = Individual Water Pump: 
stopped if unit is satisfied
0
1
1
255
0 = 9600 Baud / 1 = 19200 Baud / 2 = 
0
2
0 = No parity, 1 stop bit / 1 = Odd parity, 
1 stop bit / 2 = Even parity, 1 stop bit / 
0
5
3 = No parity, 2 stop bits / 4 = Odd parity, 
2 stop bits / 5 = Even parity, 2 stop bits
0
600
0
9999
Range
Range description
0 = Disable
1 or -1 = Power Limitation Switch
2 or -2 = Off Peak Switch
3 or -3 = Loadshed Request Switch
4 or -4 = Solar Input Switch
5 or -5 = DHW Thermal Switch (request)
-10 to 10
6 or -6 = DHW Timed Override Button
7 or -7 = DHW Anti-Legionella Cycle Request Button
8 or -8 = DHW Priority Switch
9 or -9 = External Alarm Indication
10 or -10 = Boost Mode Request Switch
Positive values correspond to Normally Open contact
Negative values correspond to Normally Closed contact
0 = Disabled
1 = Unit in Alert (still able to run)
2 = Unit in Alarm (Fail mode)
3 = Unit is in Standby (Satisfied)
4 = Unit is running (Cool, Heat, DHW, Defrost)
5 = Unit is running in Cool Mode
6 = Unit is running in Heat Mode
0 to 13
7 = Unit is running in DHW Mode
8 = Unit is running in Defrost Mode
9 = Additional Pump
10 = Boiler command
11 = Electric heater satge #3 (EH3)
12 = DHW Heater
13 = Output controlled by customer (via JBus/Modbus)
Range
Default
[No/Yes]
0 [No]
38400 Baud
600
N.A.
Unit
Table
-6
-
MSL_CONF
30
s
MSL_CONF
30
s
MSL_CONF
2
-
MSL_CONF
-
N.A.
11
-
JBUSCONF
0
-
JBUSCONF
0
-
JBUSCONF
s
JBUSCONF
0
32 bits SOFTPROT
0
-
SOFTPROT