6 -ALARM DESCRIPTION
Description
75
Inverter Fault - DC over voltage
76
Inverter Fault - Heatsink over temperature
77
Inverter Fault - AC under voltage
78
Inverter Fault - PFC over current
79
Inverter Fault - AC over voltage
80
Inverter Fault - PFC unbalanced current
81
Inverter Fault - Stator over heat
82
Inverter Fault - Printed board over temp
83
Inverter Fault - IPM temp sensor error
Inverter Fault - Input Wire Miss (three-
84
phases)
88
Inverter Fault - Other Inverter alarm
89
Real Time Clock corrupted
90
Invalid configuration                  
91
Invalid configuration - Wrong Unit Type
92
Invalid configuration - Wrong Unit Type
93
Invalid configuration - Wrong Supply Type
Invalid configuration - Wrong Inverter 
95
Model
Invalid configuration - Wrong Hydronic 
96
configuration
Invalid configuration - Compressor Map 
97
Failure
Invalid configuration - Configuration not 
98
allowed for Master/Slave
Invalid configuration - Master/Slave Wrong 
99
Addressing
100
Emergency Stop
101
External alarm
Inverter Minor Fault - Compressor Current
200
Limit
201
Inverter Minor Fault - ID Current Limit
Inverter Minor Fault - PFCM temp sensor
202
error
Inverter Minor Fault - IMP temp sensor
203
error
204
Inverter Minor Fault - Input Current Limit
205
Inverter Minor Fault - PFC over current
206
Inverter Minor Fault - AC over voltage
210
TD inconsistent value
213
TR inconsistent value
214
TS inconsistent value
232
Flow Switch alert                   
240
Leak Detection Alert
245
Lower Fan running at wrong speed
246
Upper Fan running at wrong speed
68
Reset type
Stop
x
Stop
x
Stop
x
Stop
x
Stop
x
Stop
X
Stop
X
Stop
X
Stop
X
Stop
X
Stop
X
Continue X
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
When correct configuration 
Stop
X
detected
Stop
X
Continue X
Continue x
Continue x
Continue x
Continue x
Continue x
Continue x
Continue x
Continue X
Continue X
Continue X
Continue X
Continue X
Continue X
Continue X
Investigation / corrective actions
Comment
1. Stop and disconnect the unit
2. Check coil cleanliness
3. Check inverter heatsink cleanliness
1. Check main input power voltage
1. Check main input power voltage
1. Stop and disconnect the unit
2. Check coil cleanliness
3. Check inverter heatsink cleanliness
1. Stop and disconnect the unit
2. Check main input power connection 
(L1/L2/L3)
1. Check pump parameter settings
1. Check Master / Slave settings
1. Check Master / Slave settings
1. Check TD sensor and its connection
1. Check TR sensor and its connection
1. Check TS sensor and its connection
1. Check if water loop installation is 
correct (air venting, valve position...)
2. Check water static pressure
3. Check if water filter is not clogged
4. Check Flow switch connection and 
operation
1. Check that impeller rotation is not
impeded
2. Check if coil is not fouled
1. Check that impeller rotation is not
impeded
2. Check if coil is not fouled