7 -PARAMETERS OVERVIEW
Par.
Modbus Mnemonic Description
045 002DH MOD_STAT System Mode Status
047 002FH
mod_ovr
System Mode Override
048 0030H
setpoint
Current Setpoint
049 0031H
RESET
User Adjust Temperature
050 0032H
IAT_OFF
IAT Offset
051 0033H
CTRL_PNT Control Point
052 0034H CTRL_TMP Control Temp
053
ui_init
User Interface Init Req.
Compressor Mode
061 003DH
cmp_req
Request
064 0040H
cap_ovr
Capacity Override
065 0041H
cap_tmr
Capacity Timer
066 0042H
CAP_T
Total Capacity
067 0043H
DEM_LIM Demand Limit
Frequency Reduction
068 0044H FREQ_RED
Mode
069 0045H
RUNNING Unit Running Status
071 0047H
pmv_ovr
PMV Override
072 0048H
fan_ovr
Fan Override
073 0049H
cmp_ovr
Compressor Override
70
Min
Max
0=Off, 1 = Cool, 2 = Heat, 4 = DHW, 5 = 
Booster Cool, 6 = Booster Heat,
7 = Defrost, 8 = Purge, 9 = Drying, 20 = 
Home Anti-Freeze, 21 = Cool Satisfied, 
22 = Heat Satisfied, 24 = DHW Satisfied, 
0
109
29 = Drying Satisfied, 100 = Off Fail, 101 
= Cool Fail, 102 = Heat Fail, 104 = DHW 
Fail, 105 = Booster Cool Fail, 106 = 
Booster Heat Fail, 107 = Defrost Fail, 
108 = Purge Fail, 109 = Drying Fail
0 = No override, 1 = Home Anti-Freeze 
Protection, 2 = Water Loop Freeze 
Protection, 3 = Water sampling, 4 = 
0
12
Compressor Heating (due to long stop 
period), 11 = Off Peak Requested, 12 = 
Solar Mode Active
5
60
-5
5
-4
4
5
60
-40
115,6
0
1
0 = Off, 1 = Cool, 2 = Heat, 4 = DHW, 7 
= Defrost, 20 = Anti-Freeze, 21 = Cool 
0
50
Satisfied, 22 = Heat Satisfied, 24 = DHW 
Satisfied, 50 = Stator Heating
0 = No override, 1 = Power Up Delay, 2 
= Compressor Minimum On time
3 = Compressor Minimum Off time, 4 = 
Mode Change Delay, 5 to 8 = 
Compressor Starting Sequence, 9 = 
Compressor Stopping Delay, 10 = Null 
11 = Frequency Reduction active, 12 = 
Maximum Power Exceeded, 13 = 
Maximum current exceeded, 14 = 
Inverter overcurrent or overtemp, 15 = 
Compressor stator heating after long
16 = Compressor stator heating on, 19 = 
0
204
PMV Control on TD at warmup, 20 = 
Defrost, 21 = Free Defrost, 22 = 
Post-defrost, 30 to 34 = Envelop 
protection in heating, 39 = Minimum OAT 
for Heating, 42 to 48 = Envelop 
protection in heating, 52 to 54 = Envelop 
protection in cooling, 57 to 58 = Freeze 
Protection in Cooling, 60 to 64 = Envelop 
protection in cooling, 70 = Water Flow 
Protection, 100 = System Alarm, 101 = 
Compressor or Inverter Alarm, 102 = 
Configuration Error (Factory), 201 = 
Rating Cool, 202 = Rating Heat, 203 = 
Rating Ramp Cool, 204 = Rating Ramp 
0
100
0
100
0
1
0
1
0 = No override, 3 = SST too high, 4 = 
SST too low, 5 = SH too low, 6 = SH too 
0
99
high, 7 = Compressor Frequency steady, 
98 = Closing overrun, 99 = Recalibration
0 = no override, 1 = pre-start ventilation, 
2 = post-ventilation, 11 = High OAT in 
0
50
Cooling, 21 = High SST in Heating, 50 = 
0 = No override, 1 = Ramp down, 2 = 
0
50
Ramp up, 50 = Stator Heating
Range
Default
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
Demand Limit
stop
Heat
[No/Yes]
[No/Yes]
Anti-sticking
Unit
Table
-
STATUS
-
STATUS
0
°C
STATUS
0
K
STATUS
0
K
STATUS
0
°C
STATUS
0
°C
STATUS
-
STATUS
-
LOADFACT
-
LOADFACT
s
LOADFACT
%
LOADFACT
%
LOADFACT
-
LOADFACT
-
LOADFACT
-
LOADFACT
-
LOADFACT
-