Riello NXHP Series Installation, Operation And Maintenance Instructions page 71

Table of Contents

Advertisement

Available languages

Available languages

7 -PARAMETERS OVERVIEW
Par.
Modbus Mnemonic Description
081 0051H
pmp_ovr
Pump Override
082 0052H
flow_err
Water Flow Failure
083 0053H
dtstp
Current DeltaT Setpoint
084 0054H
delta_t
Water Delta Temperature
085 0055H
PMP
Water Pump Speed
088 0058H
ADD_PMP Additional Pump status
091 005BH
back_ovr
Backup Override
092 005CH
back_flg
Backup Authorized flag
093 005DH
warmtime Booster Warm Up timer
094 005EH BACK_CAP Backup Capacity
Heat/Cool Switch Status
101 0065H ONOFF_SW
 - Heat = contact opened
 - Cool = contact closed
Heat/Cool Switch Status
102 0066H
HC_SW
 - Heat = contact opened
 - Cool = contact closed
Eco/Normal Switch 
Status
103 0067H
ECO_SW
 - Normal = contact 
opened
 - Eco = contact closed
Day/Night Switch Status
104 0068H NIGHT_SW
 - Day = contact opened
 - Night = contact closed
105 0069H
SAFE_SW Safety Switch Status
106 006AH
FLOW_SW Flow Switch Status
107 006BH
CUST_DI7 Customized DI#7 Status
108 006CH
CUST_DI8 Customized DI#8 Status
109 006DH
CUST_DI9 Customized DI#9 Status
110 006EH
RED_SW Power Limitation Switch
111 006FH OPEAK_SW Off Peak Hour Switch
112 0070H LSHED_SW Loadshed Request
Switch
113 0071H SOLAR_SW Solar Input Switch
DHW_
114 0072H
DHW Thermal Sw. (tank)
THSW
DHW Timed Override
115 0073H DHW_TOVR
Switch
DHW Anti-Legionella
116 0074H
DHW_ANTI
Req.
117 0075H
DHW_SW DHW Priority Switch
118 0076H EXALM_SW External Alarm Switch
119 0077H BOOST_SW Boost Mode Request Sw.
120 0078H
inv_type
Inverter Model Number
121 0079H
inv_soft
Inverter Soft version
122 007AH
inv_sofb
Inverter Soft version B
Min
Max
-1 = Pump Control disabled, 0 = No 
override, 1 = Compressor Still Running, 
2 = Flow Switch Failure, 3 = Pump 
Stopping Delay, 4 = Anti-Sticking, 5 = 
6 = Very Low OAT, 7 = Defrost Active, 
run the pump at maximum speed, 8 = 
Boiler Active (compr. stopped), stop the 
pump, 9 = DHW Active, 10 = Master/
Slave active
11 = Water Sampling, 12 = Purge Mode, 
-1
100
13 = Freeze protection alarm #50/52, run 
the pump, 14 = Pump stopped due to 
Compr. or Inverter failure, 15 = DHW 
Valve moving, run the pump, 16 = Water 
Control Point reached, control pump on 
CTRL_PNT, 17 = Pump stopped due to 
M/S communication failure , 18 = High 
LWT in Heating, 19 = Low LWT in 
Heating, 20 = Power up delay, 21 = High 
Temp protection, 22 = High SST in 
cooling, 100 = Emergency stop
0
1
[Normal/Alarm]
0
100
0
1
-1
100
0
1
0
1800
0
100
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
1
[Open/Close]
0
65535
0
65535 Integer format. Example 41488 (0xA210)
0
65535 Integer format. Example 45569 (0xB201)
Range
Default
Low OAT
N.A.
N.A.
N.A.
[No/Yes]
N.A.
N.A.
Unit
Table
-
PMP_STAT
-
PMP_STAT
K
PMP_STAT
K
PMP_STAT
%
PMP_STAT
-
PMP_STAT
-
BCK_STAT
-
BCK_STAT
s
BCK_STAT
%
BCK_STAT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INPUT
-
INV_MISC
-
INV_MISC
-
INV_MISC
71