4 -OPERATION
f - DHW schedule
Refer to WUI end user manual or DHW schedule parameters (P720 to P732, see § 7.1 )
Example of DHW scheduling
Step nb
MON
1
X
2
X
3
X
4
1
2
3
MON
TUE
WED
THU
FRI
SAT
SUN
Hol.
DHW regular setpoint
DHW Eco Setpoint
Anti-legionella
Space heating/cooling
4.2.15 - Master/Slave
a- Installation
Master/slave installation permits connection for multiple units in
parallel: one master unit can control several slave units.
This  kind  of  installation  must  comprise  the  same  unit  size  (for 
example all 4 kW units or all 12 kW units, but not a mix of different 
sizes).
The master / slave operation is incompatible with Domestic Hot 
Water production.
Only the Master unit can be fitted with user interface options. If 
the Slave units have been ordered with a user interface, then it is 
necessary to disconnect it.
Additional  common  leaving  water  temperature  sensor  must  be 
installed on site, on the common piping.
Accessory
Resistance = 5 KOhms
Characteristics
Cable length = 15 m
Electrical
- Refer to § 3.7 Master/Slave installation
connection
- Refer to § 3.7 Master/Slave installation
Configuration
The RS485 communication cable (not supplied) must be connected 
on each unit.
58
Day of week and holyday
TUE
WED
THU
X
X
X
X
X
X
X
X
X
4
5
6
7
8
FRI
SAT
X
X
X
X
X
X
9
10
11
12
13
14
b- Control
All units installed in the same master/slave group share the same
operating mode as well as the same setpoint.
The  Master  unit  is  connected  to  a  user  interface  which  can  be 
installed remotely. The "Master" user interface is a decision point 
for all other units in the same master/slave group, which means 
that the operating mode (cooling / heating) and the water setpoint 
defined by the master will be transmitted to other "slave" units.
When there are at least two units configured in the master/slave 
assembly, it is possible to define how compressors are started. 
Three compressor control methods are available.
Compressors can be started:
Based on address configuration: The Master unit is started first. 
Then, slave units will be started sequentially (beginning with slave 
1 and ending with, for example, slave 3). When stopping, the last 
slave is stopped first – the Master is the last unit stopped.
According to wear factor: Units are started sequentially based on 
the wear factor. As system demand increases, the unit with the 
lowest wear factor is started first, when system demand decreases 
capacity, the unit with, the highest wear factor is stopped first.
Simultaneously: All  units  are  started  and  stopped  at  the  same 
time. Compressor frequency is increased or decreased
simultaneously on all units.
For more details on Master /Slave icon display on WUI, refer to 
WUI end-user manual.
CAUTION:
In the case of master/slave communication failure, the Master
will either run in the standalone mode or it will continue to
operate with other Slave units that are still communicating.
The affected Slave unit will stop all of its operations.
Start time
SUN
Hol.
X
02:30
X
15:00
X
20:30
X
06:00
15
16
17
18
19
20
End time
06:30
17:00
22:30
10:00
21
22
23