7 -PARAMETERS OVERVIEW
Par.
Modbus Mnemonic Description
Period 8 DOW
694 02B6H
DOW8
(MTWTFSSH) 
695 02B7H
TOD8
Start from
 0=Away, 1=Sleep, 
696 02B8H
OCC8
2=Home
701 02BDH
dhw_type Domestic Hot Water Type
DHW 3-way Valve run 
702 02BEH
dhw_vlvr
time
703 02BFH
dhw_leg
DHW Anti-Legionella
704 02C0H
dhw_prio
DHW Priority Config.
705 02C1H
dhw_max DHW Maximum Runtime
DHW Minimum Pump
706 02C2H
dhw_vmin
Speed
DHW Maximum Pump
707 02C3H
dhw_vmax
Speed
dhw_dtsp DHW Pump DeltaT
708 02C4H
Setpoint
709 02C5H
dhw_sens DHW Tank Sensor Type
710 02C6H
dhw_bias DHW Tank Sensor Bias
711 02C7H
dhw_bck
DHW Electric Backup
720 02D0H DHW_OVR Timed Override Hours
DHW_
Period 1 DOW
721 02D1H
DOW1
(MTWTFSSH) 
722 02D2H DHW_TOD1 From
723 02D3H DHW_END1 To
DHW_
Period 2 DOW
724 02D4H
DOW2
(MTWTFSSH) 
725 02D5H DHW_TOD2 From
726 02D6H DHW_END2 To
DHW_
Period 3 DOW
727 02D7H
DOW3
(MTWTFSSH) 
728 02D8H DHW_TOD3 From
729 02D9H DHW_END3 To
DHW_
Period 4 DOW
730 02DAH
DOW4
(MTWTFSSH) 
731 02DBH DHW_TOD4 From
732 02DCH DHW_END4 To
741 02E5H
msl_cod
Mst/Slv Activation Code
742 02E6H
ms_sel
Master/Slave Selection
743 02E7H
slv1_add
Slave #1 Address
744 02E8H
slv2_add
Slave #2 Address
745 02E9H
slv3_add
Slave #3 Address
746 02EAH
cap_strt
Capa. To Start Next Unit
747 02EBH
cap_stop
Capa. To Stop Next Unit
751 02EFH
casc_typ
Cascade Type
752 02F0H
ms_h_kp
M/S Heat Proport. Gain
753 02F1H
ms_h _ti
M/S Heat Integral Time
754 02F2H
ms_h _ts
M/S Heat Sampling Time
Min
Max
00000000 11111111
00:00
23:59
0
2
0=Away, 1=Sleep, 2=Home
0 = No DHW management, 1 = Diverting 
0
2
Valve, 2 = No Diverting Valve (Stand-
0
240
0
1
0
1
-1
720
19
100
19
100
2
20
0 = Thermal Switch, 1 = DHW Sensor 
(thermistor 10 KΩ), 2 = DHW Sensor 
0
3
(thermistor 5 KΩ), 3 = DHW Sensor 
-5
5
0
1
-1 = Schedule disable, 0 = Schedule 
-1
24
enable, 1 to 24 = Timed override hours
00000000 11111111 bit7 = Monday ... bit1= Sunday, bit0 = 
00:00
23:59
00:00
24:00
00000000 11111111
00:00
23:59
00:00
24:00
00000000 11111111
00:00
23:59
00:00
24:00
00000000 11111111
00:00
23:59
00:00
24:00
0
2
0 = Disable, 1 = Master, 2 = Slave
0
239
0
239
0
239
30
75
1
25
Reserved for future use
0 = Starting Master First, then first Slave 
   Stopping Last Slave to first Slave, then 
0
2
1 = Starting/stopping units according to 
2 = All units are started/stopped at the 
0,001
10
10
240
10
240
Range
Default
see above
00000000
N.A.
alone DHW)
[Disable/Enable]
[No/Yes]
N.A.
N.A.
N.A.
(thermistor 3 KΩ)
N.A.
[Disable/Enable]
00000000
Holiday
N.A.
N.A.
see above
N.A.
N.A.
see above
N.A.
N.A.
see above
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
N.A.
to last Slave.
Master.
wear factors.
same time.
Unit
Table
-
OCC_SCHD
00:00
hh:mm OCC_SCHD
0
OCC_SCHD
0
-
DHW_CONF
30
s
DHW_CONF
0
-
DHW_CONF
0
-
DHW_CONF
240
min
DHW_CONF
19
%
DHW_CONF
100
%
DHW_CONF
7
K
DHW_CONF
1
-
DHW_CONF
0,0
K
DHW_CONF
0
K
DHW_CONF
-1
-
DHW_SCHD
-
DHW_SCHD
00:00
hh:mm DHW_SCHD
00:00
hh:mm DHW_SCHD
-1
-
DHW_SCHD
00:00
hh:mm DHW_SCHD
00:00
hh:mm DHW_SCHD
-1
DHW_SCHD
00:00
hh:mm DHW_SCHD
00:00
hh:mm DHW_SCHD
-1
-
DHW_SCHD
00:00
hh:mm DHW_SCHD
00:00
hh:mm DHW_SCHD
0
-
N.A.
0
-
MSL_CONF
0
-
MSL_CONF
0
-
MSL_CONF
0
-
MSL_CONF
75
%
MSL_CONF
25
%
N.A.
1
-
MSL_CONF
6
-
MSL_CONF
30
s
MSL_CONF
30
s
MSL_CONF
79