4 -OPERATION
Water setpoint configuration
The water setpoint calculation can be based on:
1/ Predefined Climatic Curves depending on OAT: climatic curves already preconfigured in the control logic.
2/ Fixed Water Setpoint: using a fixed value for each occupancy mode.
3/ Custom Climatic Curve depending on OAT: define customized climatic curves in function of the application.
4/ Offset on climatic curves (predefined and customer)
1/ Predefined climatic curves
COOLING: If the cooling climatic curve [P586] is configured to "1" or "2", the water setpoint will be calculated according to the 
selected cooling climatic curve.
Two predefined cooling climatic curves are available:
Climatic Curve
K1
K2
Cooling Climatic Curves
■ If OAT is invalid (not transmitted by the Inverter, out-of-range 
value,  etc.),  the  Water  Setpoint  is  equal  to  the  current  Min. 
Water Temp.
■ If OAT is above the current Maximum OAT threshold, the Water 
Setpoint is equal to the current Max. Water Temp.
HEATING: If the heating climatic curve [P581] is configured to a parameter from "1" to "12", the water setpoint will be calculated 
according to the selected heating climatic curve.
Twelve predefined heating climatic curves are available:
Climatic Curve
K1
K2
K3
K4
K5
K6
K7
K8
K9
K10
K11
K12
52
Min. OAT
Max. OAT
20°C
40°C
20°C
40°C
OAT (°C)
Min. OAT
Max. OAT
-7°C
20°C
-5°C
20°C
-9°C
20°C
-8°C
20°C
-5°C
20°C
0°C
20°C
-20°C
20°C
-20°C
20°C
-12,7°C
20°C
-5,9°C
20°C
-1,5°C
20°C
3,5°C
20°C
Min. Water Temp
5°C
10°C
The  climatic  curve  corresponds  to  the  water  setpoint  in  Home 
mode. To define the other occupancy modes, it is necessary to 
configure Cool Sleep Offset [P405] and Cool Away Offset [P406]:
K1
K2
Cooling Climatic Curve in function
Min. Water Temp
20°C
20°C
20°C
40°C
40°C
40°C
22°C
23°C
24°C
25°C
26°C
27°C
Max. Water Temp
10°C
18°C
of occupancy mode
P405
OAT (°C)
Max. Water Temp
38°C
33°C
45°C
50°C
55°C
60°C
42°C
55°C
60°C
60°C
60°C
60°C
Application
FCU's
UFC
Home
Sleep
Away
P406
Application
UFH
UFH
FCU's
FCU's
Radiators
Radiators
FCU's
Radiators
Radiators
Radiators
Radiators
Radiators