4 -OPERATION
Example:
Heating Climatic Curves (K7 to K8)
■ If OAT is invalid (not transmitted by the Inverter, out-of-range
value, etc.), the Water Setpoint is equal to the current Max.
Water Temp.
■ If OAT is above the current Maximum OAT threshold, the Water
Setpoint is equal to the current Min. Water Temp.
2/ Fixed water setpoint
If the cooling climatic curve [P586] or the heating climatic curve [P581]is configured to "-1", the water control point will be determined
according to the Occupancy mode.
The water setpoint can be configured in two ways:
■ By direct access to the WUI (refer to WUI end-user manual)
■ By accessing the parameter menu via WUI or JBus or Proprietary Protocol (refer to § 7. Parameter Overview)
COOLING
WUI Occupancy
Water setpoint on WUI direct access
Cool Home Setpoint
Cool Sleep Setpoint
Cool Away Setpoint
HEATING
WUI Occupancy
Water setpoint on WUI direct access
Heat Home Setpoint
Heat Sleep Setpoint
Heat Away Setpoint
K7
K8
OAT (°C)
The climatic curve corresponds corresponds to the water setpoint
in Home mode. To define the other occupancy modes, it is
necessary to configure Heating Sleep Offset [P402] and Heating
Away Offset [P403]:
Heating Climatic Curve in function
of occupancy mode
Range
Water setpoint on parameter menu
5 to 20°C
Cool Home Setpoint [P404]
Cool Sleep Offset [P405]
Cool Away Offset [P406]
Range
Water setpoint on parameter menu
20 to 75°C
Heat Home Setpoint [P401]
Heat Sleep Offset [P402]
Heat Away Offset [P403]
Home
Sleep
Away
OAT (°C)
Range
5 to 20°C
0 to 10°C
0 to 10°C
Range
20 to 75°C
-20 to 0°C
-20 to 0°C
53