Riello NXHP Series Installation, Operation And Maintenance Instructions page 54

Table of Contents

Advertisement

Available languages

Available languages

4 -OPERATION
3/ Custom climatic curve
COOLING: If the cooling climatic curve [P586] is configured 
to "0", the water setpoint will be calculated according to the 
custom cooling climatic curve.
This  custom  cooling  climatic  curve  can  be  defined  using  the 
following parameters:
Parameter
Description
P587
Custom Minimum OAT
P588
Custom Maximum OAT
P589
Custom Minimum Water Temp
P590
Custom Maximum Water Temp
Example:
Custom Cooling Climatic Curve
■ If  OAT  is  invalid,  the  Water  Setpoint  is  equal  to  the  Custom 
Minimum Water Temp [P589].
■ If OAT is above the current Maximum OAT threshold, the Water 
Setpoint is equal to the Custom Maximum Water Temp [P590].
■ If Minimum OAT is greater or equal to Maximum OAT threshold, 
the Water Setpoint is equal to the Custom Maximum Water
Temp [P590].
HEATING: If the heating climatic curve [P581] is configured 
to "0", the water setpoint will be calculated according to the 
custom heating climatic curve.
This  custom  heating  climatic  curve  can  be  defined  using  the 
following parameters:
Parameter
Description
P582
Custom Minimum OAT
P583
Custom Maximum OAT
P584
Custom Minimum Water Temp
P585
Custom Maximum Water Temp
54
Default
Min.
20°C
0°C
35°C
24°C
10°C
5°C
18°C
5°C
Default
min
max
OAT (°C)
Default
Min.
-7°C
-30°C 10°C
20°C
10°C
20°C
20°C
38°C
30°C
Example:
Custom Heating Climatic Curve
75
65
55
45
P585
35
Max.
25
P584
30°C
15
50°C
5
-30
20°C
20°C
■ If  OAT  is  invalid,  the  Water  Setpoint  is  equal  to  the  Custom 
Max. Water Temp [P585].
■ If OAT is above the current Maximum OAT threshold, the Water 
Setpoint is equal to the Custom Min. Water Temp [P584].
■ If Min. OAT is greater or equal to Max. OAT threshold, the Water 
Setpoint is equal to the Custom Max. Water Temp [P584].
4/ Offset on climatic curves (predefined and customer)
Two  other  parameters  are  also  configurable  to  adjust  water 
setpoint to suit customer needs: 
■ For cooling curve, Cool Minimum Water Setpoint [P589]can be 
offsetted by an offset on foot of the curve (Cool Curve Min Stp 
Offset [P410])
■ And for heating curve, Heat Maximum Water Setpoint [P585] 
can be offsetted by an offset on head of the curve (Heat Curv 
Max Stp Offset [P409])
Custom Cooling Climatic Curve :
Offset on foot of the curve
Max.
30°C
40°C
Heating Cooling Climatic Curve :
75°C
Offset on head of the curve
-20
-10
0
10
P582
P583
OAT (°C)
P410
OAT (°C)
P409
OAT (°C)
Default
min
max
20
30

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxhp 004Nxhp 006Nxhp 008Nxhp 010Nxhp 012Nxhp 014

Table of Contents