Riello NXHP Series Installation, Operation And Maintenance Instructions page 72

Table of Contents

Advertisement

Available languages

Available languages

7 -PARAMETERS OVERVIEW
Par.
Modbus Mnemonic Description
141 008DH
inv_comm Comm. with Inverter
143 008FH
inv_trip
Inverter Fault Trip Code
144 0090H
inv_stat
Inverter Operating State
145 0091H
inv_alt
Inverter Alert Status
146 0092H
inv_alm
Inverter Alarm Status
147 0093H
pfc_stat
PFC Status
148 0094H
cmp_stat
Compressor Status
149 0095H
htr_stat
Stator Heater Status
150 0096H
pwr_stat
 Power Save Status
151 0097H
dc_stat
DC Discharge Status
152 0098H
cfg_stat
 Config. Request Status
153 0099H
cmp_spd
Compressor Speed
154 009AH
fan1_spd
Lower Fan Speed
155 009BH
fan2_spd
Upper Fan Speed
156 009CH
dc_volt
DC Link Voltage
157 009DH
ac_volt
AC Line Voltage
158 009EH
ac_curr
AC Line Current
159 009FH
ac_powr
AC Line Power
Compressor Phase
160 00A0H
cmp_curr
Current
161 00A1H
fluxcurr
Flux Weakening Current
162 00A2H
torqcurr
Torque Current
163 00A3H
pfc_temp
PFC Module Temperature
164 00A4H
ipm_temp IPM Module Temperature
165 00A5H
fan1_sig
Lower Fan Control Signal
166 00A6H
fan2_sig
Lower Fan Control Signal
167 00A7H
htr_volt
Stator Heating Voltage
168 00A8H
htr_time
Stator Heater Timer
Circuit Board
169 00A9H
pcb_temp
Temperature
170 00AAH
inv_td
Discharge Temperature
Compressor Speed
180 00B4H
cmp_dem
Demand
181 00B5H
cmph_dem Stator Heater Demand
Lower Fan Speed 
182 00B6H
fan1_dem
Demand
Upper Fan Speed
183 00B7H
fan2_dem
Demand
DC Link Discharge
184 00B8H DC_DISCH
Command
190 00BEH
max_pwr
Maximum Allowed Power
191 00BFH
watercap
Water Capacity
192 00C0H
elec_pwr
Electric Absorbed Power
193 00C1H
cop_eer
Efficiency (COP/EER)
194 00C2H
boost_c
Boost Mode Time Credit
DHW_
201 00C9H
DHW Mode
MODE
202 00CAH
dhw_ovr
DHW Override
203 00CBH
dhw_dem DHW Demand from Tank
72
Min
Max
0
1
[Normal/Alarm]
0
1
0
1
[Normal/Alarm]
0
1
0
1
0
1
0
1
0
1
0
1
0
7200
0
1000
0
1000
0
7200
0
8200
0
1000
0
1000
0
1
-1
120
0
2
0 = Eco, 1 = Anti-Legionella, 2 = Regular
-1 = DHW disabled, 0 = DHW Operating 
, 1 = DHW Not Operating (SHC Mode or 
No demand), 2 = DHW Valve moving, 3 
= DHW Operating with EHS Only, 10 = 
-1
100
No SHC Demand checking, 50 = Heat 
Mode not allowed, 51 = DHW not 
allowed due to Loadshed, 52 = DHW not 
allowed due to Solar production, 100 = 
0
1
Range
Default
[Off/On]
0
0
[Off/On]
0
[Off/On]
0
[Off/On]
0
[Off/On]
0
[Off/On]
0
[Off/On]
0
0
0
0
[Off/On]
DHW Fail
[No/Yes]
Unit
Table
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
-
INV_STAT
rpm
INV_STAT
rpm
INV_STAT
rpm
INV_STAT
V
INV_STAT
V
INV_STAT
A
INV_STAT
KW
INV_STAT
A
INV_STAT
A
INV_STAT
A
INV_STAT
°C
INV_STAT
°C
INV_STAT
V
INV_STAT
V
INV_STAT
V
INV_STAT
s
INV_STAT
°C
INV_STAT
counts INV_STAT
rpm
INV_STAT
mA
INV_STAT
rpm
INV_STAT
rpm
INV_STAT
-
QCK_TEST
KW
POWER
KW
POWER
KW
POWER
KW
POWER
min
POWER
-
DHW_STAT
-
DHW_STAT
-
DHW_STAT

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nxhp 004Nxhp 006Nxhp 008Nxhp 010Nxhp 012Nxhp 014

Table of Contents