General Information Regarding the Wiring
Examples for the use of conductors:
▶
Motors with resolver
LIYCY 3 x 2 x 0.14 or 4 x 2 x 0.14 for motors with integrated thermal contact. Con-
ductors: shielded, twisted in pairs. Twist mode: sine/sine, cosine/cosine, rotor/rotor
and, if necessary, thermal contact/thermal contact.
For delicate applications we recommend additional shielding of the separate pairs.
▶
Motors with incremental encoder
LIYCY 5 x 0.14 or 7 x 0.14 for motors with integrated thermal contact.
▶
Motors with Hall sensors and tachometer generator
LIYCY 9 x 0.14 or 12 x 0.14 for motors with integrated thermal contact.
11.2.4
Cables for the External Ballast Resistor
The cables of the external ballast resistor of R
is longer than 20 cm a shielded cable must be used.
86
and +UB must be twisted. If the cable
EX
Drive System SD2S - Hardware Description 0362x49xx / 0362129xx