ELECTRICAL CONNECTIONS
4

4.6 Signal cable to converter

Each sensor rail has a signal cable which has to be connected, optional via a cable extension
(splitter) box, to the signal converter. The inner cables are colour-coded and labelled to apply a
correct connection of the acoustic paths.
INFORMATION!
Connect the cable to the connector with similar numeral marking.
Field version
Figure 4-8: Connect signal cable
Construction of console (F-version)
Figure 4-9: Inserting cable and secure with clamp on shielding bush
1 Signal cable (blue or black)
2 Cable glands
3 Grounding clamps
4 Signal cable with metal shielding bush and wire marking
CAUTION!
Re-connecting of the coax connectors is limited. Make sure that the male connector on the coax
cable, is always put straight on the female connector in the connection terminal of the unit.
Continuously re-connection and/or positioning the connectors skewed to each other will damage
the inside clips of the connectors causing incorrect contact and measurement errors.
60
www.process.honeywell.com
VERSAFLOW SONIC 1000/TWS 9000
34-VF-25-07 iss.2 GLO Nov 11 US