INSTALLATION
3

3.7.4 T-section

Figure 3-4: Distance behind a T-section
1 ≥ 20 DN

3.7.5 Bends

Figure 3-5: Installation in bending pipes (90°)
INFORMATION!
Recommended installation positions are at a lowered or ascending section of the pipeline
installation. Installation at the highest point will enlarge the risk of flowmeter malfunction,
because of air/gas bubbles.
Vertical installation in combination with an open surcharge has to be avoided.
Vertical installation with a controlled back-pressure is possible.