Honeywell VERSAFLOW SONIC 1000/TWS 9000 Handbook page 121

Ultrasonic clamp-on flowmeter for liquids
Table of Contents

Advertisement

VERSAFLOW SONIC 1000/TWS 9000
No.
Function
A4 Station address
A4
station address
A5 Digital Outputs
A5
digital outputs
A5.1
measurement
A5.2
pulse value unit
A5.3
value p. pulse
A5.4
low flow cutoff
A6 GDC IR interface
A6
GDC IR interface
1 Depends on IO hardware module
34-VF-25-07 iss.2 GLO Nov 11 US
Setting / Description
for Modbus devices.
valid for all pulse outputs (terminals A, B and/or D) and totaliser 1.
1) select measurement: volume flow / mass flow
2) use for all outputs? (also use this setting for Fct. A5.2...A5.4!)
setting: No (only for pulse output D) / Yes (for all digital outputs)
selection of the unit from a list, depending on the measurement.
1) setting for pulse output D (volume or mass value per pulse)
setting: xxx.xxx in l/s or kg/s
2) Use for all outputs? Make setting, see Fct. A5.1 above!
1) setting for pulse output D (sets output value to "0")
setting: x.xxx ± x.xxx% (range: 0.0...20%)
(1st value = switching point / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
2) Use for all outputs? Make setting, see Fct. A5.1 above!
after this function has been activated an optical GDC adapter can be
connected to the LC display. After 60 seconds pass without a connection
being established or after the adapter is removed, the function is exited and
the optical keys are active again
break (exit function without connection)
activate (the IR interface adapter and interrupt the optical keys)
www.process.honeywell.com
OPERATION
6
121