Honeywell VERSAFLOW SONIC 1000/TWS 9000 Handbook page 130

Ultrasonic clamp-on flowmeter for liquids
Table of Contents

Advertisement

OPERATION
6
C4_ Status Output B or C
_ stands for 3 or 4
Error
Out Of Specification (output set, signals status of category "Error in Device" or "Application Failure" or
message
"Out Of refer to
for pipe 1
Application Failure (output set, signals status of category "Error in Device" or "Application Failure" refer
Status messages and diagnostic information
and pipe 2
to
configuratio
Flow Polarity (polarity of the current flow) /
n
Flow Over Range (over range of the flow) /
Empty Pipe (when pipe empty, output activated) /
Error in Device (output set, signals status of category "Error in Device" refer to
diagnostic information
Totaliser 1 Preset (activates when totaliser X preset value is reached) /
Totaliser 2 Preset (activates when totaliser X preset value is reached) /
Totaliser 3 Preset (activates when totaliser X preset value is reached) /
Output A (activated by the status of output Y, additional output data see below) /
Output B (activated by the status of output Y, additional output data see below) /
Output C (activated by the status of output Y, additional output data see below) /
Output D (activated by the status of output Y, additional output data see below) /
Off (switched off) /
Power Overrange /
Power Polarity /
Calculated Flow Polarity
C4._.1
mode
C4._.3
invert signal
C4._.4
information
C4_ Limit switch B or C
_ stands for 3 or 4
C4._.1
measurement
C4._.2
threshold
C4._.3
polarity
C4._.4
time constant
C4._.5
invert signal
C4._.6
information
C4._.7
simulation
130
Status messages and diagnostic information
on page 146)
only if output is activated when error occurs and depending on pipe
configuration 1 or 2 pipes.The output shows the following measuring
conditions:
Select: Off (activated output: switch closed) / On (activated output: switch
open)
Serial no. of the I/O board, software version no. and production date of the
circuit board
select:
Volume Flow / Mass Flow / Flow Speed,Power / Calculated Flow / Velocity of
Sound / Gain / SNR / diagn flow speed, diagn VoS, diagn gain, diagn SNR
Set measured value polarity, please note flow direction in C1.6.2!
xxx.x ±x.xxx (format and unit depend on the measurement, see above)
(1st value = threshold / 2nd value = hysteresis),
condition: 2nd value ≤ 1st value
Set polarity, please note Flow Direction
Select: Both Polarities (plus and minus values are displayed) /
Positive Polarity (display for negative values = 0) /
Negative Polarity (display for positive values = 0) / Absolute Value (always
displays positive, with both negative and positive values)
Range: 000.1...100 s
Select:
Off (activated output: switch closed) /
On (activated output: switch open)
Serial no. of the I/O board, software version no. and production date of the
circuit board
Sequence see B1._ Limit switch, simulation; on,off,cancel
www.process.honeywell.com
VERSAFLOW SONIC 1000/TWS 9000
on page 146 )/
on page 146) /
Status messages and
34-VF-25-07 iss.2 GLO Nov 11 US