VERSAFLOW SONIC 1000/TWS 9000

4.9.3 Pulse output and frequency output

INFORMATION!
Depending on the version, the pulse and frequency outputs must be connected passively or
actively or according to NAMUR EN 60947-5-6! Which I/O version and inputs/outputs are
installed in your signal converter are indicated on the sticker in the cover of the terminal
compartment.
• All outputs are electrically isolated from each other and from all other circuits.
• All operating data and functions can be adjusted.
• Passive mode:
External power supply required: U
I ≤ 20 mA at f ≤ 10 kHz (over range up to f
I ≤ 100 mA at f ≤ 100 Hz
• Active mode:
Use of the internal power supply: U
I ≤ 20 mA at f ≤ 10 kHz (over range up to f
I ≤ 20 mA at f ≤ 100 Hz
• NAMUR mode: passive in accordance with EN 60947-5-6, f ≤ 10 kHz,
over range up to f
• Scaling:
Frequency output: in pulses per time unit (e.g. 1000 pulses/s at Q
Pulse output: quantity per pulse.
• Pulse width:
symmetric (pulse duty factor 1:1, independent of output frequency)
automatic (with fixed pulse width, duty factor approx. 1:1 at Q
fixed (pulse width adjustable as required from 0.05 ms...2 s)
• Forward/reverse flow measurement (F/R mode) is possible.
• All pulse and frequency outputs can also be used as a status output / limit switch.
INFORMATION!
For further information refer to Connection diagrams of inputs and outputs on page 74
Technical data on page 172
to
DANGER!
For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.
34-VF-25-07 iss.2 GLO Nov 11 US
≤ 32 VDC
ext
= 24 VDC
nom
≤ 12 kHz
max
.
www.process.honeywell.com
ELECTRICAL CONNECTIONS
≤ 12 kHz)
max
≤ 12 kHz)
max
100%
);
100%
) or
and refer
4
71