Program The Totalisers - Honeywell VERSAFLOW SONIC 1000/TWS 9000 Handbook

Ultrasonic clamp-on flowmeter for liquids
Table of Contents

Advertisement

VERSAFLOW SONIC 1000/TWS 9000
Manually entering the temperature values
• If there are no temperature sensors available for connecting, set the "Temperature input" to
"Fixed".
Δ process input
C1.11
Flow mode
Temperature inputs fixed
Temperature inputs fixed
Temperature inputs fixed
Temperature inputs fixed
Supply temperature
• Set the location of the flow sensor (supply or return side of the installation) in order to
calculate the correct specific heat of the liquid.
• Check if the shown fluid is correct.
INFORMATION!
The type of fluid is set in the flow sensor installation wizard. In case the fluid is set to water-
glycol mixture in the flow sensor installation wizard the concentration of glycol in water can be
set in the heating/cooling setup menu.
Δ process input
C1.14
Temperature input
current inputs
current inputs
current inputs
current inputs
A: supply B: return
Flow sensor

3.11.3 Program the totalisers

• Go to menu C5 I/O Totalisers and select a totaliser for counting energy.
Δ totaliser
C5._.1
Function of totaliser
Function of totaliser
Function of totaliser
Function of totaliser
sum totaliser
Measurement
• At the "Function of totaliser", select "Sum" for counting both positive and negative energy
flows.
• Select "+ counter" for only counting positive energy flows.
• Select "- counter" for only counting negative energy flows.
• At the "Measurement" option, select "Power". The energy value counter unit is kJ.
34-VF-25-07 iss.2 GLO Nov 11 US
www.process.honeywell.com
INSTALLATION