Honeywell VERSAFLOW SONIC 1000/TWS 9000 Handbook page 83

Ultrasonic clamp-on flowmeter for liquids
Table of Contents

Advertisement

VERSAFLOW SONIC 1000/TWS 9000
CAUTION!
Observe connection polarity.
Status output / limit switch active, modular I/Os
• U
= 24 VDC
int
• I ≤ 20 mA
≤ 47 kΩ
• R
L
• open:
I ≤ 0.05 mA
closed:
U
0, nom
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
Figure 4-26: Status output / limit switch active S
Status output / limit switch passive, modular I/Os
• Any connection polarity.
• U
= 32 VDC
ext
• I ≤ 100 mA
• R
L, max
R
L, min
• open:
I ≤ 0.05 mA at U
closed:
U
0, max
U
0, max
• The output is open when the device is de-energized.
• X designates the connection terminals A, B or D, depending on the version of the signal
converter.
Figure 4-27: Status output / limit switch passive S
34-VF-25-07 iss.2 GLO Nov 11 US
= 24 V at I = 20 mA
= 47 kΩ
= (U
- U
) / I
ext
0
max
= 32 VDC
ext
= 0.2 V at I ≤ 10 mA
= 2 V at I ≤ 100 mA
ELECTRICAL CONNECTIONS
a
p
www.process.honeywell.com
4
83