Mounting - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Too much torque damages the screw clamps and/or controller housing
Do not use power tools during the installation.
Materials required for mounting and wiring
Materials
Four screw clamps
Wires and connectors
Cable ties
2.3

Mounting

The controller is designed for mounting in the front panel.
Panel cutout:
• Length: 219.0 mm
• Height: 158.0 mm
• Tolerance: ± 0.3 mm
1. Insert the controller in the panel.
2. Insert the screw clamps:
3.b.1
3. Tighten the screw clamps to 0.19 Nm. Do not tighten the clamps to more than 0.19 Nm.
User manual 4189341341B EN
3.b.2
3.b.3
*Click*
NOTICE
Used for
Mounting the controller in the front panel
Wiring third party equipment to the controller terminals
Securing wiring
3.b.4
Page 9 of 89