Deif SGC 420 User Manual page 26

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Parameter
(Digital) Activation
(Digital) Activation
Delay
(LOP) Circuit Fault
Action
(LOP) Lube Oil
Pressure Calibration
Table
Analogue Input 2
Parameter
Use Input As
(Digital) Source
Name
(Digital) Polarity
(Digital) Action
(Digital) Activation
(Digital) Activation
Delay
(FLS) Low Fuel Level
Shutdown
(FLS) Shutdown
Threshold
(FLS) Low Fuel Level
Warning
User manual 4189341341B EN
Range
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 0 to 1000
Ω
Pressure: 0.0 to 10.0
Bar
Range
Not used
Digital Input K
Fuel Level Sensor
See Digital input
source selection in
this document
Auxiliary Input K
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
Enable
Disable
0 to 78 %
Enable
Disable
Default
From Monitoring On
1 s
None
-
Default
Not used
Not used
-
Close to Activate
None
From Monitoring On
1 s
Not enabled
10 %
Enabled
Description
Configure from when the digital input is
monitored.
If the input is active when the timer expires, the
controller actives the action for the digital input.
Configure the action for when there is a circuit
failure.
Configure the resistance and pressure values
for the 10 measurement points in the calibration
table.
Description
Select what to use the input as.
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Configure from when the digital input is
monitored.
If the input is active when the timer expires, the
controller actives the action for the digital input.
If this parameter is enabled, the controller shuts
down the engine when the fuel level is less than
the shutdown set point (SHUTDOWN
THRESHOLD).
The controller shuts down the engine when the
fuel level is less than this set point.
If this parameter is enabled, the controller
shows a notification when the fuel level is less
than the notification set point (NOTIFICATION
THRESHOLD).
Page 26 of 89