Parameter
Current Delay
Low Current Action
Low Current Threshold 0 to 195 A
Load Monitoring
Parameter
Overload Action
Overload Threshold
Overload Monitoring
Delay
Unbalanced Load
Action
Unbalanced Load
Threshold
Unbalanced Load
Delay
Low Load Enable
Low Load Action
Low Load Trip
Low Load Return
Low Load Delay
User manual 4189341341B EN
Range
0 to 180 s
None
Notification
Warning
Electrical Trip
Shutdown
Range
None
Notification
Warning
Electrical Trip
Shutdown
10 to 200 %
1 to 600 s
None
Warning
Electrical Trip
Shutdown
Notification
5 to 200 %
1 to 600 s
Enable
Disable
None
Warning
Electrical Trip
Shutdown
Notification
1 to 99 %
2 to 100 %
1 to 3600 s
Default
0 s
None
20 A
Default
None
90 %
1 s
None
5 %
1 s
Not enabled
None
50 %
51 %
1 s
Description
When the delay timer expires, the action for
high current is activated if the current is more
than high current set point.
The action that occurs when the current is less
than the low current set point.
The action for low current is activated when the
current is less than this set point.
Description
The action that occurs when the load is more
than the overload set point.
The action for overload is activated when the
load is more than this set point.
If the load is more than the set point for
overload when the time expires, the action for
overload is activated.
The action that occurs when the load is more
than the set point for unbalanced load.
The action for unbalanced load is activated
when the load is more than this set point.
If the load is more than the set point for
unbalanced load when the time expires, the
action for unbalanced load is activated.
If this parameter is enabled, the configured
action for low load is activated.
The action that occurs when low load is
detected. Low load is detected when the load is
less than the set point for low load trip.
The set point for low load. When the load is less
than this set point, the action for low load is
activated.
If the action for low load is a warning, the
controller stops monitoring low load when the
load is more than this set point.
If the load is less than the set point for low load
when the time expires, the low load action is
activated.