Engine - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Parameter
(UF) Trip
(UF) Return
Over-frequency
(OF) Trip
(OF) Return
OF Delay
3.5.8

Engine

Crank Disconnect
Parameter
Start Attempts
Disconnect on Oil
Pressure Sensor
Monitor Pressure
Sensor Before Crank
Pressure Sensor
Monitoring Threshold
Monitor Pressure
Switch Before Crank
Disconnect on Oil
Pressure Switch
Pressure Switch
Transient Time
Crank Disconnect At
Alt Frequency
Crank Disconnect At
Engine Speed
Disconnect On
Charging Alt Voltage
User manual 4189341341B EN
Range
10.0 to 59.0 Hz
11.0 to 60.0 Hz
Yes
No
26.0 to 75.0 Hz
25.0 to 74.0 Hz
0 to 100 s
Range
1 to 9
Enable
Disable
Enable
Disable
0.5 to 10 bar
Enable
Disable
Enable
Disable
0.0 to 3.0 s
10 to 70 Hz
150 to 4000 RPM
Enable
Disable
Default
45 Hz
47 Hz
Yes
55 Hz
52 Hz
10 s
Default
3
Not enabled
Not enabled
4 bar
Not enabled
Not enabled
1.5 s
20 Hz
600 RPM
Not enabled
Description
frequency is less than the under-frequency set
point.
If the mains frequency is less than this set
point, there is a mains failure.
The mains returns when the mains frequency is
more than this set point.
If this parameter is enabled, the controller
detects a mains failure when the mains
frequency is more than the over-frequency set
point.
If the mains frequency is more than this set
point, there is a mains failure.
The mains returns when the mains frequency is
less than this set point.
If the frequency is more than the over-
frequency set point when this timer expires, the
action for over-frequency is activated.
Description
Number of attempts to crank the engine.
If this parameter is enabled, the crank is
disconnected when the oil pressure is more
than the oil pressure set point.
If this parameter is enabled, the oil pressure is
monitored before the engine starts. If the oil
pressure is more than the set point, the engine
cannot start.
Configure the set point for the oil pressure.
If this parameter is enabled, the oil pressure is
monitored before the engine starts. If the
pressure switch is open, the controller activates
a high oil pressure alarm.
If this parameter is enabled, the crank
disconnects if the oil pressure is high.
If the oil pressure is high after this timer
expires, the crank is disconnected.
If the frequency is more than this set point
during cranking, the controller disconnects the
crank.
If the engine speed is more than this set point
during cranking, the controller disconnects the
crank.
If this parameter is enabled, the crank is
disconnected when the charging alternator
Page 40 of 89