Deif SGC 420 User Manual page 84

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

No.
Output source
8
Close mains contactor
9
Mains failure
10
Common alarm
11
Common electrical trip
12
Common shutdown
13
Common warning
14
Cooling down
15
Dig In A
16
Dig In B
17
Dig In C
18
Dig In D
19
Dig In E
20
Dig In F
21
Dig In G
22
Dig In H
23
Dig In I
24
Dig In J (LOP resistive)
Dig In K (Analogue input - fuel
25
level)
Dig L (Analogue input - engine
26
temp.)
27
Dig In M (Aux. sensor 1)
28
Dig In N (Aux. sensor 2)
29
Dig In O (Aux. sensor 3)
30
Dig In P (Aux sensor 4)
31
Emergency stop
32
Stop solenoid
33
Fail to start
34
Fail to stop
35
Fuel relay
36
Gen available
37
L1 phase OV shutdown
38
L1 phase UV shutdown
39
L2 phase OV shutdown
40
L2 phase UV shutdown
User manual 4189341341B EN
Description
This output is activated when the digital input for close mains/open genset
is activated in manual mode.
This output is activated when there is a mains failure.
This output is activated when one of the alarm types is activated.
This output is activated when there is an active electrical trip alarm.
This output is activated when there is an active shutdown alarm.
This output is activated when there is an active warning alarm.
This output is activated when the cooldown period of the genset is
initiated. The output is activate for the duration of the period.
This output is activated when digital input A is activated.
This output is activated when digital input B is activated.
This output is activated when digital input C is activated.
This output is activated when digital input D is activated.
This output is activated when digital input E is activated.
This output is activated when digital input F is activated.
This output is activated when digital input G is activated.
This output is activated when digital input H is activated.
This output is activated when digital input I is activated.
This output is activated when digital input J is activated.
This output is activated when digital input K is activated.
This output is activated when digital input L is activated.
This output is activated when digital input M is activated.
This output is activated when digital input N is activated.
This output is activated when digital input O is activated.
This output is activated when digital input P is activated.
The output is activated when the emergency stop is activated.
This output is activated when the stop solenoid output is high.
This output is activated when the fail to start alarm is activated.
This output is activated when the fail to stop alarm is activated.
This output is activate when the fuel relay is active.
This output is activated when the timer for the warm up delay expires.
This output is activated when the over-voltage shutdown alarm for phase L1
is activated.
This output is activated when the under-voltage shutdown alarm for phase
L1 is activated.
This output is activated when the over-voltage shutdown alarm for phase
L2 is activated.
This output is activated when the under-voltage shutdown alarm for phase
L2 is activated.
Page 84 of 89