Deif SGC 420 User Manual page 23

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Parameter
Language
Display
Parameter
Contrast
Power Save Mode
Communication
Parameter
Communication Mode
Server ID
Baud rate
Parity Bit
Site Battery Monitoring
Parameter
Battery Monitoring
Low Voltage Threshold 12.0 to 60.0 V
Battery Monitoring
Delay
Genset Run Duration
User manual 4189341341B EN
Range
English
Chinese
Range
0 to 100 %
Enable
Disable
Range
None
Modbus
1 to 247
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
None
Even
Odd
Range
Enable
Disable
5 to 300 s
1 to 720 minutes
Default
English
Default
80 %
Not enabled
Default
None
2
9600 bps
None
Default
Not enabled
60.0 V
20 s
270 minutes
Description
have resolved the condition that activated the
alarm.
You can change the display language if the
controller supports multiple languages.
Description
Configure the display contrast with this
parameter.
If this parameter is enabled, the controller turns
off the LCD backlight after an adjustable time.
This is only when the engine is not operating.
You can configure the adjustable timer on the
controller or with the smart connect software
here: Timers > General > Power Save
Mode Delay.
Description
Select the communication mode.
Select the server ID for Modbus.
Select the baud rate for the serial
communication.
Select the parity bit for the serial
communication.
Description
If this parameter is enabled, the controller
monitors the site battery voltage. The voltage is
also shown on the controller.
This is the set point for the site battery voltage.
If the voltage is less than this set point, there is
a battery failure.
This is the delay timer for the site battery
voltage. If the voltage is still low when the timer
expires, there is a battery failure.
During a site battery failure, the genset
operates for the Genset Run duration. This is
only for AUTO mode.
Page 23 of 89