Modes Of Operation; Operation Mode; Auto Mode; Island - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

4. Modes of operation

4.1

Operation mode

The controller has two running modes:
• AUTO: The controller operates automatically, and the operator cannot initiate sequences manually.
• Manual: The operator has to initiate all sequences. You can do this with the buttons, Modbus commands, or digital
inputs.
4.2

AUTO mode

In AUTO mode, you can select these functions:

• Island

• Engine drive
• Automatic mains failure (AMF)
• Site battery monitoring
• Cyclic
• Remote start/stop
• Auto exercise
To go to AUTO mode, push the Mode selection button until AUTO mode is shown on the display.
4.2.1
Island
The controller operates in island when:
• Mains monitoring and site battery monitoring are not enabled.
• Cyclic and auto exercise are not enabled.
In the smart connect software, go to Mains > Configuration > Mains monitoring and make sure that mains
monitoring is not enabled. To make sure that auto exercise is not enabled for events 1 and 2, go to Module > Auto
Exercise > Event 1/Event 2.
The controller automatically starts the genset and closes the generator breaker at a digital start command. When the stop
command is given, the generator breaker opens, and the genset is stopped after a cooling down period.
Use a digital input to activate and deactive the start and stop commands. You cannot use the display buttons in AUTO
mode.
User manual 4189341341B EN
G
Page 48 of 89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents