Digital Outputs - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

No.
Source
15
V-belt broken switch
16
Mains contactor latched
17
Gen contactor latched
18
Battery charger failure
19
Smoke alarm
20
Remote alarm mute
21
Remote alarm acknowledge
22
Stop and panel lock
23
External panel lock
24
Generator load inhibit
25
Mains load inhibit
26
Regeneration SW inhibit signal
27
Idle mode enable
28
Alternate nominal switch
9.2

Digital outputs

No.
Output source
1
Disable
2
Sounder alarm
3
Battery over volt
4
Battery under volt
5
Charge alt shutdown
6
Charge alt warning
7
Close gen contactor
User manual 4189341341B EN
Description
• Mains monitoring is enabled and there is a mains failure. The input is
deactivated. The is still a mains failure and the mains breaker opens.
When this input is activated an alarm is shown on the display. You can
configure the alarm type.
When this input is activated, the mains breaker closes and the genset
breaker opens.
When this input is activated, the genset breaker closes and the mains
breaker opens.
This input is activated when there is a battery charge failure and the mains
is OK. An alarm occurs and the controller initiates the configured action, for
example, a warning.
When this input is activated, an alarm occurs and the controller initiates the
configured action, for example, a shutdown.
Mutes all present alarms, and the alarm LED on the display stops flashing.
Acknowledges all present alarms, and the alarm LED on the display stops
flashing.
The controller initiates the stop sequence when this input is activated and
locks the display. The operator cannot push the buttons on the display.
The controller changes the running mode to AUTO and locks the display.
The operator cannot use the display.
When this input is activated, the generator cannot take the load. If the
genset is operating when the input is activated, then genset cools down
and stops.
When this input is activated, the mains cannot take the load. If the mains is
operating when the input is activated,
This is an input for CAN bus.
You can activate idle mode with this input.
If this input is activated, the default nominal settings switch to the
alternative nominal settings.
Description
The output is not used.
This output is high when an alarm is generated. The output is activate for
the duration of the alarm.
This output is activated when there is an active alarm for battery over-
voltage.
This output is activated when there is an active alarm for batter under-
voltage.
This output is activated when there is an active shutdown alarm for charge
failure.
This output is activated when there is an active warning alarm for charge
failure.
This output is activated when the digital input for close genset/open mains
is activated in manual mode.
Page 83 of 89