Wiring; Typical Wiring - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Terminal
Text
50
MAINS V N
51
MAINS V L3
52
MAINS V L2
53
MAINS V L1
54
GEN V N
55
GEN V L3
56
GEN V L2
57
GEN V L1
58
CAN L (Reserved)
59
CAN H (Reserved)
60
Reserved
61
Reserved
2.5

Wiring

2.5.1

Typical wiring

NOTE
The wiring diagram is an example. Use the wiring diagram for the application during installation.
Fuses
• F1: 2 A DC max. time-delay fuse/MCB, c-curve
• F4, F5: 2 A AC max. time-delay fuse/MCB, c-curve.
Relays
• Protect the breaker relays for the genset and mains against 4 kV surges as described in the IEC 61000-4-5 standard.
• Protect relay cards used with the controller against reverse battery voltages.
User manual 4189341341B EN
Description
Voltage input from mains neutral
Voltage input from mains phase L3
Voltage input from mains phase L2
Voltage input from mains phase L1
Voltage input from gen neutral
Voltage input from Gen L3
Voltage input from Gen L2
Voltage input from Gen L1
CAN Low
CAN High
-
-
Connector
BCP-508-7GN-4PA
BCP-508-4GN
Page 12 of 89