Mains - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

3.5.7

Mains

Configuration
Parameter
Mains Monitoring
Mains AC System
Phase Reversal
Detection
Phase Reversal Action
Partial Healthy
Detection
Mains PT Enable
Mains PT Primary
Mains PT Secondary
Voltage Monitoring
Parameter
Under-voltage
Under-Voltage Trip
Under-Voltage Return
Over-voltage
Over-Voltage Trip
Over-Voltage Return
Voltage Monitoring
Delay
Frequency Monitoring
Parameter
Under-frequency
User manual 4189341341B EN
Range
Enable
Disable
Single phase (L1-N)
3-phase (L1-L2-L3-N)
Split-phase (L1-N-L2)
Split-phase (L1-N-L3)
2-phase (L1-L2-N)
2-phase (L1-L3-N)
3-phase (L1-L2-L3)
Enable
Disable
None
Notification
Enable
Disable
Enable
Disable
100 to 25000
100 to 700
Range
Yes
No
50 to 298 V phase-
neutral
52 to 300 V phase-
neutral
Yes
No
102 to 350 V phase-
neutral
100 to 348 V phase-
neutral
0 to 100 s
Range
Yes
No
Default
Enabled
3-phase
Not enabled
None
Not enabled
Not enabled
100
100
Default
Yes
55 V
57 V
Yes
280 V
270 V
10 s
Default
Yes
Description
If this parameter is enabled, the controller
monitors the mains voltage and frequency.
Select the phase system for the mains.
If this parameter is enabled, a phase reversal is
detected if the phase sequence is not L1-L2-L3.
Configure the action for phase reversal
detection.
If this parameter is enabled, a mains failure is
not detected if one or two of the phases fail.
This is only for a 3-phase system.
Enable this parameter, if the application
includes a mains power transformer (PT).
Configure the PT primary value.
Configure the PT secondary value.
Description
If this parameter is enabled, the controller
detects a mains failure when the mains voltage
is less than the under-voltage set point.
If the mains voltage is less than this set point,
there is a mains failure.
The mains returns when the mains voltage is
more than this set point.
If this parameter is enabled, the controller
detects a mains failure when the mains voltage
is more than the over-voltage set point.
If the mains voltage is more than this set point,
there is a mains failure.
The mains returns when the mains voltage is
less than this set point.
If the voltage is more than the over-voltage set
point when this timer expires, the action for
over-voltage is activated.
Description
If this parameter is enabled, the controller
detects a mains failure when the mains
Page 39 of 89