3.5.7
Mains
Configuration
Parameter
Mains Monitoring
Mains AC System
Phase Reversal
Detection
Phase Reversal Action
Partial Healthy
Detection
Mains PT Enable
Mains PT Primary
Mains PT Secondary
Voltage Monitoring
Parameter
Under-voltage
Under-Voltage Trip
Under-Voltage Return
Over-voltage
Over-Voltage Trip
Over-Voltage Return
Voltage Monitoring
Delay
Frequency Monitoring
Parameter
Under-frequency
User manual 4189341341B EN
Range
Enable
Disable
Single phase (L1-N)
3-phase (L1-L2-L3-N)
Split-phase (L1-N-L2)
Split-phase (L1-N-L3)
2-phase (L1-L2-N)
2-phase (L1-L3-N)
3-phase (L1-L2-L3)
Enable
Disable
None
Notification
Enable
Disable
Enable
Disable
100 to 25000
100 to 700
Range
Yes
No
50 to 298 V phase-
neutral
52 to 300 V phase-
neutral
Yes
No
102 to 350 V phase-
neutral
100 to 348 V phase-
neutral
0 to 100 s
Range
Yes
No
Default
Enabled
3-phase
Not enabled
None
Not enabled
Not enabled
100
100
Default
Yes
55 V
57 V
Yes
280 V
270 V
10 s
Default
Yes
Description
If this parameter is enabled, the controller
monitors the mains voltage and frequency.
Select the phase system for the mains.
If this parameter is enabled, a phase reversal is
detected if the phase sequence is not L1-L2-L3.
Configure the action for phase reversal
detection.
If this parameter is enabled, a mains failure is
not detected if one or two of the phases fail.
This is only for a 3-phase system.
Enable this parameter, if the application
includes a mains power transformer (PT).
Configure the PT primary value.
Configure the PT secondary value.
Description
If this parameter is enabled, the controller
detects a mains failure when the mains voltage
is less than the under-voltage set point.
If the mains voltage is less than this set point,
there is a mains failure.
The mains returns when the mains voltage is
more than this set point.
If this parameter is enabled, the controller
detects a mains failure when the mains voltage
is more than the over-voltage set point.
If the mains voltage is more than this set point,
there is a mains failure.
The mains returns when the mains voltage is
less than this set point.
If the voltage is more than the over-voltage set
point when this timer expires, the action for
over-voltage is activated.
Description
If this parameter is enabled, the controller
detects a mains failure when the mains
Page 39 of 89