Outputs; Timers - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Parameter
(0-5 V) Calibration
Table

3.5.4 Outputs

Outputs #
Parameter
Source
On Activation
3.5.5

Timers

Cranking
Parameter
Crank Hold Time
Crank Rest Time
Manual Start Delay
Auto Start Delay
Start/Stop
Parameter
Safety Monitoring
Delay
Warm-Up Delay
Return To Mains Delay
Engine Cooling Time
Stop Action Time
Additional Stopping
Time
Load Transfer Delay
User manual 4189341341B EN
Range
Shutdown
Voltage: 0 to 5 V
Value: 0 to 1000
Range
See Digital output
source selection in
this document
Energise
De-energise
Range
1 to 255 s
2 to 60 s
0 to 300 s
0 to 43200 s
Range
10 to 60 s
0 to 60 s
0 to 600 s
0 to 300 s
10 to 120 s
0 to 120 s
1 to 60 s
Default
-
Default
-
De-energise
Default
5 s
5 s
3 s
3 s
Default
10 s
3 s
5 s
5 s
30 s
10 s
1 s
Description
Configure the voltage values for 10
measurement points in the calibration table.
Description
Select an output source from the list.
Select what the status of the output source is
when it is active. You can select if it is
energised or de-energised.
Description
Configure for how long the engine cranks.
The time between each crank.
When this timer expires in manual mode, the
engine starts to crank.
When this timer expires in AUTO mode, the
engine starts to crank.
Description
The engine safety parameters are not
monitored during the Safety monitoring delay.
The timer starts after crank disconnect.
When the alternator voltage and frequency are
OK, the load is transferred to the alternator.
There's a warm-up delay before the load is
transferred.
The controller closes the mains breaker when
the return to mains delay timer expires.
When the engine cooling timer expires, the
engine stops.
The time duration for the stop action sequence.
Additional time added to the engine stop
sequence.
The time it takes to transfer the load to the
mains or genset.
Page 33 of 89